Omron C200HW-CLK21 ユーザーズマニュアル

ページ / 401
94
C200HX/HG/HE Controller Link Units
Section 4-3
4-3-1
Overview
Node Address
Baud Rate and Operating Level
Baud Rate
Note
Factory default setting is in bold. 
Always leave pin 3 OFF.
Operating Level
Terminating Resistance
4-3-2
Node Addresses
Set the node addresses of each Unit on the Network using the rotary switches
on the front of the Unit. The node address is used to identify each node in the
Network can be set to any number between 01 and 32.
1
CLK21
X10
1
X10
0
SW1
ON
BD
H
BD
L
SHLD
RUN
ERC
INS
SD
TER
ERH
M/A
LNK
RD
TER
SW
#0, #1
1
2
3
4
RSV
BAUD
     RATE
0
1
23
4
1
X10
1
X10
0
SW1
ON
#0, #1
1
2
3
4
RSV
BAUD
     RATE
0
1
23
4
NODE NO.
Setting range
Nodes
01 to 32 (default is 01)
All nodes in the Network
Pins
Baud rate
Maximum 
transmis-
sion dis-
tance
Nodes
Pin 1
Pin 2
OFF OFF
2 Mbps
500 m
Set same 
rate for all 
nodes in the 
Network.
ON
OFF
1 Mbps
800 m
OFF
ON
500 Kbps
1 km
ON
ON
Cannot be set.
Pin 4
Operating 
level
Nodes
OFF 
(factory 
default)
Level 1
All nodes in the Network
Set so that only one Communi-
cations Unit is set to the same 
level in the same PLC.
ON
Level 0
Bottom 
switch
Terminating 
resistance
Nodes
OFF 
(factory 
default)
Not connected
All nodes in the Network
Turn ON the terminating resis-
tance at the nodes at both 
ends of the Network and turn it 
OFF at all other nodes.
ON
Connected
1's digit
10's digit
NODE NO.
X10
1
X10
0
0
1