Omron CJ1W-EIP21 ユーザーズマニュアル

ページ / 464
249
Receiving Explicit Messages
Section 9-2
9-2-1
List of PLC Object Services
PLC Objects provide the following services.
Status Read/Write for CPU Units
Services
Service 
code
Class ID
Instance ID
Request 
service data
Contents
CPU Unit Informa-
tion Read 
0E Hex
C4 Hex
(2F Hex)
(See note.)
00 Hex
Attribute ID = 
64 Hex
Reads the operating mode of the 
CPU Unit.
Attribute ID = 
65 Hex
Reads if there is a fatal or non-fatal 
error in the CPU Unit.
Attribute ID = 
66 Hex
Reads CPU Unit model.
CPU Unit Write 
10 Hex
Attribute ID = 
64 Hex,
Attribute Value
Changes the operating mode of the 
CPU Unit.
Attribute ID = 
65 Hex
Attribute Value
Clears errors.
CPU Unit Status 
Read 
40 Hex
None
Reads the detailed status of the CPU 
Unit.
Operation status: Stop, run, CPU 
standby
Operating modes: PROGRAM, MON-
ITOR, RUN 
Fatal error information: Error flags, 
including memory errors, I/O bus 
errors, system errors
Messages: Message No. when MSB 
instruction executed by CPU Unit
Error codes: Error code for the most 
serious errors
Error messages: Messages stored in 
CPU Unit when FAL/FALS instruction 
executed