VFDB 4132 Series Brake Modules 
Instruction Sheet 
X
 
Preface 
Thank you for choosing DELTA’s brake module. VFDB brake units are applied to 
absorb the motor regeneration energy when the three-phase induction motor stops by 
deceleration. With VFDB brake unit, the regeneration energy will be dissipated in 
dedicated brake resistors. To prevent mechanical or human injury, please refer to this 
instruction sheet before wiring. VFDB brake units are suitable for DELTA AC Motor 
Drives VFD Series 230V/460V/575V. VFDB brake units need to be used in conjunction 
with BR series brake resistors to provide the optimum brake characteristics. VFDB 
brake units (4132) are approved by Underwriters Laboratories, Inc. (UL) and Canadian 
Underwriters Laboratories (cUL). The content of this instruction sheet may be revised 
without prior notice. Please consult our distributors or download the most updated 
version at http://www.delta.com.tw/industrialautomation. 
Y
 
Specifications 
VFDB 4132 Brake Units 
Specification 
460V Series 
Max. Motor Capacity (kW) 
132 
Max. Discharge Current (A) 10%ED 
240 
Continuous Discharge Current (A) 
75 
Outpu
Rating 
Braking Start-up Voltage (DC) 
618/642/667/690/725/750±6V 
Input 
Rating 
DC Voltage 
480-750VDC 
Min. Equivalent Resistor for Each Brake Unit 
3.4Ω 
Heat Sink Overheat Temperature 
Temperature exceeds +95
 o
C (203
o
F) 
Alarm Output for Overheat 
Relay contact 3A250VAC/30VDC 
(RA, RC) 
Power Charge Display 
ON until the bus (P-N) voltage is 
below 50VDC 
Prote
cti
on 
Over-current Protection Level 
320A 
Installation Location 
Indoor (no corrosive gases, metallic 
dust) 
Operating Temperature 
-10
o
C~+50
o
C (14
o
F to 122
o
F) 
Storage Temperature 
-20
o
C ~+60
o
C (-4
o
F to 140
o
F) 
Humidity 
Less than 90% Non-condensing 
Environmen
Vibration 
9.8m/s
2
 (1G) under 20Hz / 2m/s
2
 
(0.2G) at 20~50Hz 
Mechanical Configuration 
Wall-mounted enclosed type IP10 
 
 
Brake Resistors 
Model no. 
Specification 
BR1K5W005 1500W 
5.0Ω 
BR1K2W6P8 1200W 
6.8Ω 
BR1K2W008 1200W 
8.0Ω 
BR1K5W040 1500W 
40Ω 
BR1K0W050 1000W 
50Ω 
BR1K0W075 1000W 
75Ω 
Z
 
Dimensions 
3.1 Brake resistor 
 
3.2 Brake unit 
VFDB4132
CHARGE       
ACT OC
OH
 
 
 
[
 
Internal Components and Terminals
 
4.1 Internal Components 
 
4.2 Wire Gauge for Terminals 
Circuit 
Terminals 
Wire Gauge AWG 
(mm
2
Screw
Torque 
Power Input
Circuit 
DC+, DC- 
4~6AWG 
(13.3~21.2mm
2
M8 
30 kgf-cm   
(26 in-lbf) 
Brake 
Resistor 
B1, B2 
4~6AWG 
(13.3~21.2mm
2
M8 
30 kgf-cm   
(26 in-lbf) 
Output M1, M2 
SLAVE 
Circuit 
Input S1, 
S2 
18~20AWG 
(0.8~0.5mm
2
(With shielded wires) 
M2 
4 kgf-cm   
(3 in-lbf) 
Fault 
Circuit 
RA, RC 
18~20AWG 
(0.8~0.5mm
2
M2 
4 kgf-cm   
(3 in-lbf) 
\
 
Basic Wiring Diagram 
Note 1: When the AC motor drive is used with DC reactor, please refer to the wiring 
             diagram in the AC drive user manual for wiring terminal DC+ of brake unit.
Note 2: 
 wire terminal DC- to the neutral point of power system.
DO NOT
NFB
R/L1
MC
S/L2
T/L3
O.L.
MC
SA
Thermal Overload
Relay or Temperature switch
Surge Absorber
R/L1
S/L2
T/L3
VFD Series
R/L1
S/L2
T/L3
IM
+(P)
-(N)
E.F
DCM
Motor
DC+
DC-
RA
RC
VFDB 
Brake
Unit
B1
B2
BR
O.L.
Thermal 
Overload 
Relay
Brake
Resistor
Temperature Switch
 
NOTE
 
„
 
For safety consideration, install an overload relay between the brake unit and the 
brake resistor. In conjunction with the magnetic contactor (MC) prior to the drive, 
it can perform complete protection against abnormality. 
„
 
The purpose of installing the thermal overload relay is to protect the brake resistor 
from damage due to frequent brake, or due to brake unit keeping operating 
resulted from unusual high input voltage. Under such circumstance, just turn off 
the power to prevent damaging the brake resistor. 
„
 
Please refer to the specification of the thermal overload relay. 
„
 
The alarm output terminals (RA, RC) of the brake unit will be activated when the 
temperature of the heat sink exceeds 95
°C. It means that the temperature of the 
installation environment may exceed 50
°C, or the brake %ED may exceed 
10%ED. With this kind of alarm, please install a fan to force air-cooling or reduce 
the environment temperature. If the condition not due to the temperature, the 
control circuit or the temperature sensor may have been damaged. At this time, 
please send the brake unit back to the manufacturer or agency for repair. 
„
 
The AC Motor Drive and brake unit will be electrified at the same time while 
turning on the NFB (No-fuse breaker). For the operation/stop method of the motor, 
please refer to the user manual of the AC Motor Drives VFD Series. The brake 
unit will detect the inner DC voltage of the AC motor drive when it stops the motor 
by deceleration. The extra regeneration will be dissipated away rapidly by the 
brake resistor in the form of heat. It can ensure the stable deceleration 
characteristic. 
„
 
Besides, using thermal overload relay to be the protection system and brake 
resistor, temperature switch can be installed on brake resistor side as the 
protection. The temperature switch must comply with the brake resistor 
specification or contact your dealer.
 
]
 
Wiring Warnings
 
„
 
Do not proceed with wiring while power is applied to the circuit.   
„
 
The wiring gauge and distance must comply with the local regulations. 
„
 
The +(P), -(N) terminals of the AC motor drive (VFD Series), connected to the 
brake unit (VFDB), must be confirmed for correct polarity lest the drive and the 
brake unit be damaged when power on. 
„
 
When the brake unit performs braking, the wires connected to DC+, DC-, B1 and 
B2 would generate a powerful electromagnetic field for a moment due to high 
current passing through. These wires should be wired separately from other low 
voltage control circuits lest they make interference or mis-operation.
 
„
 
Inflammable solids, gases or liquids must be avoided at the location where the 
brake resistor is installed. The brake resistor had better be installed in individual 
metallic box with forced air-cooling. 
„
 
Connect the ground terminal to the Earth Ground. The ground lead must be at 
least the same gauge wire as leads DC+, DC-. 
„
 
Please install the brake resistor with forced air-cooling or the equivalent when 
frequent deceleration braking is performed (over 10%ED).   
„
 
Do NOT change any wirings and settings and touch any terminals and 
components while power is applied to avoid electric shock. 
„
 
It is recommended to use the ring terminals for main circuit wiring. Make sure the 
terminals are fastened before power on.
 
„
 
Wiring distance
 
VFD series
Max 8M
Max 5M
BR
VFDB
series
AC Motor Drive
Brake Unit
Brake Resistor
 
^
 Definition for the Brake Usage ED% 
100%
T0
T1
Brake Time
Cycle Time
ED% = T1/T0x100(%)
 
The definition of the brake usage ED(%) is to assure having enough time for the brake 
unit and brake resistor to dissipate the heat generated by brake. When the brake 
resistor heats up, the resistance would increase with temperature, and brake torque 
would decrease accordingly. 
_
 
The Voltage Settings 
1. 
Voltage setting: the power source of the brake unit is DC voltage from +(P), -(N) 
terminals of the AC motor drive. It is very important to set the voltage of the brake 
unit based on the actual input power of the AC motor drive before operation. The 
setting has a great influence on the potential of the operation voltage for the brake 
unit. Please refer to the table below. 
NOTE
   
„
 
Before changing the setting of the power voltage, make sure the power has been 
turned off. Please set power voltage as the possible highest voltage for unstable 
power system. Take 380VAC power system for example. If the voltage may be up 
to 410VAC, 415VAC should be set. 
„
 
For DELTA’s AC motor drive (VFD Series), please set parameter (Over Voltage 
Stall Prevention) as “close” to disable over-voltage stall prevention, to ensure 
stable deceleration characteristic.   
Table 1: The Selection of AC Power Voltage and Voltage Setting 
AC Power Voltage 
Brake Start-up voltage 
DC Bus (DC+, DC-) Voltage 
380VAC (460V Mode) 
618VDC 
400VAC (460V Mode) 
642VDC 
415VAC (460V Mode) 
667VDC 
440VAC (460V Mode) 
690VDC 
460VAC (460V Mode) 
725VDC 
480VAC (460V Mode) 
750VDC 
NOTE: Input Power With Tolerance  ±10% 
CHARGE ACT
OC
480V
460V
440V
415V
400V
380V
OH
Power lamp Brake lampOver-current 
      lamp
Overheat
    lamp
Input Voltage Setting 
For VFDB 4132
Factory setting: 440V
Input voltage setting for VFDB 4132
 
 
2. 
MASTER (M) /SLAVE (S) setting: the factory setting is “M”. The “S” setting is 
applied to two or more brake units in parallel, making these brake units be 
enabled/disabled synchronously. Then the power dissipation of each unit will be 
equivalent so that they can perform the brake function completely. 
 
 
In the following diagram, it shows jumper setting for the application of three brake 
units. After wiring, the jumper in the first brake unit should be set to “M” and others 
must be set to “S” to complete the system setting. 
+ P
( )     
  VFD 
Series
M1
M2
M
B1       
O.L.
DC+     
BR
-(N)
DC -
B2
M1
M2
B1       
O.L.
DC+     
BR
DC -
B2
S1
S2
S
B1       
O.L.
DC+     
BR
DC -
B2
S1
S2
S
 
480V
460V
440V
415V
400V
380V
Input Voltage Setting
M
S
MASTER/SLAVE
Setting Jumper
M1: SLAVE output signal +
M2: SLAVE output signal -
S1: SLAVE input signal +
S2: SLAVE input signal -
NOTE: Please use shielded 
            wires while wiring.
SLAVE output/input terminal Alarm output terminals
M2
M1
S2
S1
RA RC
The Position of the Jumper
 
NOTE
 
„
 
Please make sure that power is OFF before setting the jumper. 
„
 
The steps for jumper setting: 
Step 1. Remove the top cover. 
Step 2. Remove the screws on the side case (3 screws for each side). 
Step 3. Remove the screws that connected bottom case to the side case (2 
screws for each side). 
Step 4. After removing the power line of the fan, pull out the heat sink slowly until 
the jumper can be seen. Then the jumper can be set. 
`
 Brake Resistors/Units for Delta VFD 
AC Motor Drives Series 
Applicable 
Motor 
V
o
ltag
HP  kW 
Full-load 
Torque 
kg-M 
Resistor Value
Spec. for Each 
AC Motor 
Drive 
Brake Unit 
Part No. 
and 
Quantity
Brake Resistors
Part No. and 
Quantity 
Brake 
Torque
10%ED
Min. 
Equivalent 
Resistor Value 
for Each AC 
Motor Drive
Typical 
Thermal 
Overload 
Relay 
Value
120  90 52.5  13500W 
4132
1 BR1K5W005 9
120
5Ω 110A
150  110 61  21600W 
4132
1 BR1K2W008 18
120
4Ω 135A
175  132 73.5  21600W 
4132
1 BR1K2W008 18
100
4Ω 135A
215  160 89 21600W 
3.4Ω 4132
1 BR1K2W6P8 18
97 3.4Ω 160A
250  185 103 27000W 
2.5Ω 4132
2 BR1K5W005 18
115 2.5Ω 220A
460V 
300  220 122.5 27000W 
2.5Ω 4132
2 BR1K5W005 18
96 2.5Ω 220A
 
a
 Examples 
NOTE
 
„
 
Before wiring, please notice equivalent resistors value shown in the column 
“Equivalent resistors specification for each brake unit” in the above table to 
prevent damage.
 
460V 120HP 
O.L.
B1
B2
VFDB
4132
VFD900_43_
VFD900_43_ uses wi th 3 BR sets in parall el, which 3P CS 1K 5W005 brake r esistors 
ar e connected in series.
VFD
Series
+(P)
-(N)
DC+
DC-
BR
BR
BR
BR
BR
BR
BR
BR
BR
BR
BR
BR
M
BR
BR
BR
BR
BR
BR
Brake Uni t
Brake 
Resistor
Thermal O verload  Rel ay
 
460V 150HP, 175HP, 215HP 
O.L.
B1
B2
VF DB
4132
VF D1100_ 43_
VF D13 20_43_
VF D16 00_43_
VF D1100_ 43_ us es w ith 6 BR  s ets in p aral lel, w hic h 3PC S  1K2W 008 bra ke r es is to rs 
are c on nec te d  in s erie s.
VF D
Ser ies
+ (P)
-( N)
D C+
D C-
BR
BR
BR
BR
BR
BR
M
BR
BR
BR
BR
BR
BR
BR
BR
BR
BR
BR
BR
BR
BR
BR
BR
BR
BR
BR
BR
BR
BR
BR
BR
BR
BR
BR
BR
BR
BR
Bra ke U nit
T herm al Ov er load  Rel ay
Bra ke 
R esi stor
VF D16 00_43_ use s w ith 6 BR sets in pa rall el, wh ic h 3PC S 1K2W6 P8 brak e re si stor s 
are c on nec te d  in s erie s.
1 K2W00 8 brak e res is tors  
are c on nec te d  in s erie s.  
VF D13 20_43_ use s w ith 6 BR s ets in par all el, wh ic h 3PCS 
 
460V 250HP, 300HP 
VF D 
Ser ies
+ (P)  -( N)
VFD1850_43_
VFD2200_43_
VFD1850_43_ uses with 2 VF DB4132 brak e units and each  brake unit us es  with 
3 BR sets i n parall el, which 3PCS 1K5W005 brak e resis tors are connec ted  in series.
VFD2200_43_ uses with 2 VF DB4132 brak e units and each  brake unit us es  with 
3 BR sets i n parall el, which 3PCS1K5W005 brake resi stors are c onnected in s eri es .
O.L .
B1
B2
VFDB
4132
DC+ DC-
M
M1 M2
BR
BR
BR
BR
BR
BR
BR
BR
BR
O.L .
B1
B2
VFDB
4132
DC+ DC-
BR
BR
BR
BR
BR
BR
BR
BR
BR
S1 S2
S
Brak e Unit
Thermal Overload Rel ay
Thermal Overload Rel ay
Brak e Unit
Brak e 
Resis tor
Brak e 
Resis tor