Powerware SOLA 4000 ユーザーズマニュアル
SOLA 4000 - Technical Data
JUE 401269
106
IG. 2.1 - Rectifier Data
2 Rectifier Data
Technical Data / Rectifier Data
Type SOLA 4000
10
15
20
30
40
60
80
100
120
Input voltage
Tolerance
with reduced output (DC) voltage
Tolerance
with reduced output (DC) voltage
refer to system data
refer to system data
-20 %
refer to system data
-20 %
Input frequency
Tolerance
Tolerance
refer to system data
± 10 %
± 10 %
Rated input power with charged battery
- [kVA]
- [kVA]
10,8
16
21,3
32
42,7
64,1
84,8
106
127,4
Rated input current with charged battery
(380 V) [A]
(380 V) [A]
16,4
24,6
32,7
49,2
65
97,5
128,5
160,7
193
Maximum input power
- [kVA]
- [kVA]
13,5
20
26,9
39,8
53,5
80
105
132
158
Maximum input current, input voltage = 380 V
- [A]
- [A]
20,5
30,8
40,8
61,2
81,5
122
160,5
201
241
Input power factor
( nom. load, input voltage = 380V)
( nom. load, input voltage = 380V)
~ 0,83 lag.
Output control characteristics
I/U characteristic, boost charge possible
Rated output voltage
- Lead-Acid batteries
- Ni-Cd batteries
- Lead-Acid batteries
- Ni-Cd batteries
432 V/DC
436 V/DC (depending on number of cells)
436 V/DC (depending on number of cells)
Soft start
~ 10 sec.
Floating voltage regulation with load between 0
and 100%
and 100%
1 %
Output voltage ripple with battery disconnected
RMS 1 %
Max. batt. recharging current with nom. load
- [A]
- [A]
5
7,5
10
15
20
30
40
50
60
Battery charging current limitation
Complies with battery manufacturer's recommendations,
standard setting approximately 10% of rated battery capacity
standard setting approximately 10% of rated battery capacity