Appendix C
Site Preparation
Grounding Systems
107
NOTE
In some cases power distribution system green (green/yellow) wire ground conductors are too 
long and inductive to provide adequate high frequency ground return paths. Therefore, the 
server is shipped with a ground strap for connecting the system cabinet to the site grounding 
grid (customer-supplied). When connecting this ground, ensure that the raised floor is properly 
grounded.
Power panels located in close proximity to the computer equipment should also be connected to the site 
grounding grid. Methods of providing a sufficiently high frequency ground grid are described in the next 
sections.
Raised Floor Grounding
If a raised floor system is used, install a complete signal grounding grid for maintaining equal potential over 
a broad band of frequencies. The grounding grid should be connected to the equipment cabinet and electrical 
service entrance ground at multiple connection points using a minimum #6 AWG (16mm2) wire ground 
conductor.
Hewlett-Packard recommends the following approaches:
Excellent—Add a grounding grid to the subfloor. The grounding grid should be made of aluminum strips 
mounted to the subfloor. The strips should be 0.032 in. (0.08 cm) thick and a minimum of 3.0 in. (8.0 cm) 
wide.
Connect each pedestal to four strips using 1/4 in. (6.0 mm) bolts tightened to the manufacturer’s torque 
recommendation.