Honeywell UDC2500 ユーザーズマニュアル

ページ / 243
Monitoring and Operating the Controller 
94 
UDC2500 Universal Digital Controller Product Manual 
4/07 
4.5.2 Viewing the operating parameters 
Press the 
LOWER DISPLAY
 key to scroll through the operating parameters listed in Table 
4-3. The lower display will show only those parameters and their values that apply to 
your specific model. 
Table 4-3  Lower Display Key Parameter Prompts 
Lower Display  
Description 
OT XX.X 
OUTPUT—Output value is percent; for Three Position Step control, this is an 
estimated motor position and shown with no decimal place. 
SP XXXX 
LOCAL SETPOINT #1—Also current setpoint when using SP Ramp. 
2LXXXX 
LOCAL SETPOINT #2 
RSXXXX 
REMOTE SETPOINT 
2NXXXX 
INPUT 2 
DEXXXX 
DEVIATION—Maximum negative display is –999.9. 
PIDS X 
TUNING PARAMETER SELECTED SET—where X is either 1 or 2. 
HH.MM 
TIME REMAINING—Time that remains on timer in Hours.Minutes 
 
ELAPSED TIME—Time that has elapsed on timer in Hours.Minutes. 
RPXXXM 
SETPOINT RAMP TIME—Time remaining in the setpoint ramp in minutes. 
AX XXX 
AUXILIARY OUTPUT 
SnXXXX 
SP RATE SETPOINT—Current setpoint for setpoint rate applications 
BIXXXX 
BIAS—Displays the manual reset value for algorithm PD+MR.  
To BGn 
TO BEGIN—Resets Setpoint Program back to beginning of the program. 
NoTUNE 
Unit is currently not in Accutune process. 
DoSLOW 
Accutune Slow tuning process is operating. 
DoFAST 
Accutune Fast tuning process is operating. 
POSXX.XX 
Three position