Honeywell UDC2500 ユーザーズマニュアル

ページ / 243
Monitoring and Operating the Controller 
4/07 
UDC2500 Universal Digital Controller Product Manual 
105 
At the end of the tuning process, the controller immediately calculates the tuning 
constants and enters them into the Tuning group, and begins PID control with the correct 
tuning parameters.  This works with any process, including integrating type processes, 
and allows retuning at a fixed setpoint. 
4.11.1 
Tune for Simplex Outputs 
Table 4-11  Procedure for Starting “TUNE” 
Step 
Operation 
Press 
Result 
Configure LSP1 
Lower
Display
Lower
Display
Lower
Display
 
Until SP (Local Setpoint 1) shows 
in the lower display. 
 
or
 
Until LSP1 is to the desired value. 
Switch to 
“Automatic” Mode 
M-A
Reset
M-A
Reset
M-A
Reset
 
Until the “A” indicator is lighted (on 
controllers with Manual option). 
Show Tuning 
Prompt 
Lower
Display
Lower
Display
Lower
Display
 
Until “NoTUNE” is shown on lower 
display. 
Initiate Tuning 
 
Select “DoSLOW” or “DoFAST” in 
lower display. 
Tuning in operation 
Lower
Display
Lower
Display
Lower
Display
 
Upper display will flash “TUNE” as 
long as ACCUTUNE process is 
operating.  When process 
completes, tuning parameters are 
calculated and lower display will 
show “NoTune” prompt. 
 
ATTENTION 
The Accutune process may be aborted at any time by changing the lower display back to “NoTUNE” or 
by switching the controller into Manual Mode. 
 
4.11.2 
Tune for Duplex (Heat/Cool) 
Accutune for applications using Duplex (Heat/Cool) control. 
The controller must be configured to have two local setpoints unless Blended Tuning is 
desired (see below). See Subsection 3.11- Control Set Up Group for details on 
configuring two local setpoints. During tuning, the Accutune III process assumes that 
Local Setpoint 1 will cause a Heating demand (output above 50%), and the tuning 
parameters calculated for that setpoint are automatically entered as PID SET 1. Likewise, 
Accutune III assumes that Local Setpoint 2 will cause a Cooling demand (output less 
than 50%), and the tuning parameters calculated for that setpoint are automatically 
entered as PID SET 2.