Honeywell UDC2500 ユーザーズマニュアル

ページ / 243
Monitoring and Operating the Controller 
4/07 
UDC2500 Universal Digital Controller Product Manual 
109 
4.11.6 Error 
Codes 
Table 4-16  Procedure for Accessing Accutune Error Codes 
Step 
Operation 
Press 
Result 
Select Accutune 
Set-up Group 
Setup
Setup
 
Upper Display = SET  
Lower Display = ATUNE 
Go to Error Code 
Prompt 
Function
Function
Function
 
Upper Display = (an error code) 
Lower Display = ATERR 
Table 4-17 lists all the error codes, definitions, and 
fixes. 
 
Table 4-17  Accutune Error Codes 
Error Code 
(Upper Display) 
 
Definition 
 
Fix 
RUN 
ACCUTUNE RUNNING 
The Accutune process is still active (Read Only) 
NONE 
NO ERRORS OCCURRED 
DURING LAST ACCUTUNE 
PROCEDURE 
None 
IDFL 
PROCESS IDENTIFICATION 
FAILURE 
Autotune has aborted 
because an illegal value of 
GAIN, RATE, or reset was 
calculated. 
• Illegal 
Values 
– try Accutune again.  
•  untunable process -- contact local application 
engineer. 
ABRT 
CURRENT ACCUTUNE 
PROCESS ABORTED 
caused by the following 
conditions: 
a. Operator changed to 
Manual mode 
b. Digital Input detected 
c. In Heat region of output 
and a Cool output calculated 
or vice versa.
 
Try Accutune again 
SP2 
LSP2 not enabled or LSP1 or 
LSP2 not in use (only applies 
to Duplex Tuning) 
Enable LSP2 and configure the desired LSP1 and 
LSP2 setpoints.  
 
Aborting Accutune 
To abort Accutune and return to the last previous operation (SP or output level), press  
M-A/RESET
 key to abort the Accutune process.