Input Calibration 
4/07 
UDC2500 Universal Digital Controller Product Manual 
139 
Table 5-2  Voltage and Milliamp Equivalents for Input 2 Range Values 
Range Values 
Sensor Type 
PV Input Range 
0 % 
100 % 
Linear 
Milliamps 
 
4 to 20 mA 
0 to 20 mA 
 
4.00 mA 
0.00 mA 
 
20.00 mA 
20.00 mA 
Volts 
1 to   5 Volts 
0 to   5 Volts 
0 to   2 Volts 
1.00 Volts 
0.00 Volts  
0.00 Volts 
5.00 Volts 
5.00 Volts 
2.00 Volts 
 
5.3 Preliminary Information 
Disconnect the Field Wiring 
Tag and disconnect any field wiring connected to the input (#1 or #2) terminals on the 
rear of the controller. 
XXXX
R
+ 
_ 
Input 1 
Connections 
25 R
26 +
27 –
 
mA+
Volt+
Input 2 
Connections 
22 mA+ 
23 V+ 
24 – 
_ 
Input 1 
Input 2 
 
Figure 5-1  Input 1 and Input 2 Wiring Terminals 
Equipment Needed 
Table 5-3 lists the equipment you will need to calibrate the specific types of inputs that 
are listed in the table. You will need a screwdriver to connect these devices to your 
controller. 
Table 5-3  Equipment Needed 
Type of Input 
Equipment Needed 
Thermocouple 
Inputs (Ice Bath) 
•  A calibrating device with at least ± 0.02 % accuracy for use as a 
signal source such as a millivolt source. 
•  Thermocouple extension wire that corresponds with the type of 
thermocouple that will be used with the controller input. 
•  Two insulated copper leads for connecting the thermocouple 
extension wire from the ice baths to the mV source. 
•  Two containers of crushed ice. 
Thermocouple 
Inputs (T/C Source) 
•  A calibrating device with at least ± 0.02 % accuracy for use as a 
signal source such as a millivolt source. 
•  Thermocouple extension wire that corresponds with the type of 
thermocouple that will be used with controller input.