Input Calibration 
4/07 
UDC2500 Universal Digital Controller Product Manual 
149 
5.8  Restore Input Factory Calibration 
Introduction 
The factory calibration constants for all the input actuation types that can be used with 
the controller are stored in its non-volatile memory. Thus, you can quickly restore the 
“Factory Calibration” for a given input actuation type by simply changing the actuation 
type to another type and then changing it back to the original type.  
Refer to Table 5-14  Restore Factory Calibration for procedure 
ATTENTION 
A restored factory calibration overwrites any previous field calibration done for the input and 
may change the High and Low Range Limits.   
Protect your field calibration from accidental overwrites by configuring the appropriate 
LOCKOUT selection after calibration.  
See Section 3 - Configuration for specific instructions to set the lockout. 
Table 5-14  Restore Factory Calibration 
Step 
Operation 
Press 
Result 
Set LOCKOUT to 
NONE  
Setup
Setup
 
until you see
Upper Display
 = SET UP 
Lower Display
 = TUNING 
 
 
Function
Function
Function
 
Until you see: 
Upper Display
 = one of the following: 
NONE – all parameters are read/write 
CAL – all parameters are read/write except Calibration 
CONF – configuration parameters are Read Only; no writes 
permitted 
VIEW – Tuning and Setpoint Ramp parameters are 
read/write. No other parameters can be viewed. 
ALL – Tuning and Setpoint Ramp parameters are available 
for read only. No other parameters can be viewed. 
Lower Display
 = LOCK 
 
 
or
 
Until NONE is in the upper display 
Enter INPUT 1 
Setup Group 
Setup
Setup
 
until you see
Upper Display
 = SET UP 
Lower Display
 = INPUT 1 or 2 
 
 
Function
Function
Function
 
until you see
Upper Display
 = the current selection 
Lower Display
 = INxTYP 
 
 
or
 
to change the current selection to another selection 
Scroll through 
Functions 
Function
Function
Function
 
until the lower display rolls through the rest of the functions and 
returns to:  
Upper Display
 = the new selection 
Lower Display
 = INxTYP