Output Calibration 
154 
UDC2500 Universal Digital Controller Product Manual 
4/07 
6.3  Auxiliary Output Calibration 
Introduction 
Calibrate the controller so that the auxiliary output provides the proper amount of current 
over the desired range. The controller can provide an auxiliary current output range of 
from 0 mA to 21 mA and is usually calibrated at 4 mA for 0 % of output and 20 mA for 
100 % of output or any other values between 0 mA and 21 mA.  It is not necessary to re-
calibrate the controller in order to change from 4 to 20 mA operation over to 0 to 20 mA 
operation, a simple configuration change is all that is required.  See the AO RANGE 
configuration in Sub-section 3.12 for details. 
Equipment Needed 
You will need a calibrating device with whatever accuracy is required, capable of 
measuring 0 to 20 mA. 
Calibrator Connections 
Table 6-3  Set Up Wiring Procedure for Auxiliary Output 
Step 
Action 
Apply power and allow the controller to warm up 30 minutes before you calibrate. 
Set LOCK in the Tuning Set Up group to NONE. 
Tag and disconnect the field wiring, at the rear of the controller, from terminals 12 (+) 
and 13 (–). See Figure 6-2. 
Connect a milliammeter across these terminals. 
 
12
13
Milliammeter
+
_
+
_
12
13
Milliammeter
+
_
+
_
 
Figure 6-2  Wiring Connections for Calibrating Auxiliary Output