Troubleshooting/Service 
4/07 
UDC2500 Universal Digital Controller Product Manual 
161 
7.3   Power-up Tests 
What happens at power-up 
When power is applied, the controller will run three diagnostic tests. After these tests are 
completed, “TEST DONE” is displayed.  
Test Failures 
If one or more of these tests fail, the controller will go to the Failsafe Manual Mode, and 
FAILSF will flash in the lower display and a message indicating which test failed will 
appear in the lower display. Then, “DONE” will appear in the lower display. 
Three Position Step test failures 
For controller configured for Three Position Step Control with motor position indication 
and Auto-cal has never been done, the prompt CAL MTR will appear to suggest that the 
controller be calibrated.  
7.4  Status Tests 
Introduction 
When required, the results of these tests can be checked to determine the reason the 
controller has gone to Failsafe. 
How to check the status tests 
Table 7-2  Procedure for Displaying the Status Test (Numeric Code 1200) 
Results 
Step 
Operation 
Press 
Result 
Select  
STATUS 
Set Up Group 
Setup
Setup
 
Upper Display
 = READ 
Lower Display
 = STATUS 
Read the test 
results 
Function
Function
Function
 
You will see: 
Upper Display
 = NO or YES   YES indicates a failure 
Lower Display
 = FAILSAFE 
 
 
Function
Function
Function
 
Upper Display
 = PASS or FAIL 
Lower Display
 = TEST