Honeywell UDC2500 ユーザーズマニュアル

ページ / 243
Modbus Read, Write and Override Parameters plus Exception Codes 
4/07 
UDC2500 Universal Digital Controller Product Manual 
211 
 
10.7.9 Options 
Table 10-17  Set-up Group – Options 
Parameter 
Description 
Register 
Address 
Data 
Type 
Access 
Data Range or 
Enumerated Selection 
 
Hex 
Decimal 
 
 
 
Auxiliary 
Output * 
0086 134 
INT R/W  0 = None 
1 = Input 1 
2 = Input 2 
3 = PV 
4 = Deviation 
5 = Output 
6 = Setpoint 
7 = LSP 1 
8 = LSP 2 
Low Scaling 
Factor 
0031 
049 
FP 
R/W 
Within the range of the 
selected variable in ID 134 
High Scaling 
Factor 
0032 
050 
FP 
R/W 
Within the range of the 
selected variable in ID 134 
Auxiliary 
Output Range 
00EC 236 
INT  R/W 
0 = 4-20 mA 
1 = 0-20 mA