3.11   Control Set Up Group 
Introduction 
The functions listed in this group deal with how the controller will control the process 
including: Number of Tuning Parameter Sets, Setpoint Source, Tracking, Power-up 
Recall, Setpoint Limits, Output Direction and Limits, Deadband, and Hysteresis. 
Function Prompts 
Table 3-11  Table 3-12  CONTRL Group (Numeric Code 800) Function Prompts 
Function Prompt  
Lower Display 
Selection or Range of Setting 
Upper Display 
English 
Numeric 
Code 
English 
Numeric 
Code 
Parameter  
Definition 
PIDSET 801   
 
NUMBER OF TUNING PARAMETER 
SETS
—This selection lets you choose one 
or two sets of tuning constants (gain, rate, 
and reset).  NOTE:  The Tuning Group is 
automatically configured to have two PID 
sets when a Duplex Control Algorithm is 
configured. 
 
 
ONE 0 
ONE SET ONLY—Only one set of tuning 
parameters is available. Configure the values 
for: 
    Gain (proportional band), 
    Rate, 
    Reset Time, and 
    Cycle Time (if time proportional is used). 
 
 
2KBD 1 
TWO SETS KEYBOARD SELECTABLE
Two sets of tuning parameters can be 
configured and can be selected at the 
operator interface or by using the Digital 
Inputs. 
Press  LOWER DISPLAY key until you see 
PID SET1 or PID SET2 then press 
or
 to switch between sets. Configure 
the values for: 
 
Gain, Rate, Reset, Cycle Time 
 
Gain #2, Rate #2, Reset #2, Cycle 
#2  
Time