Honeywell UDC2500 ユーザーズマニュアル

ページ / 243
Configuration 
4/07 
UDC2500 Universal Digital Controller Product Manual 
67 
3.12   Options  Group 
Introduction 
The Options group lets you configure the remote mode switch (Digital Inputs) to a 
specific contact closure response, or configure the Auxiliary Output to be a specific 
selection with desired scaling. 
Function Prompts 
Table 3-13  OPTION Group (Numeric Code 900) Function Prompts 
Function Prompt  
Lower Display 
Selection or Range of Setting 
Upper Display 
English 
Numeric 
Code 
English 
Numeric 
Code 
Parameter  
Definition 
AUXOUT 901 
 
 
AUXILIARY OUTPUT SELECTION 
This selection provides an mA output 
representing one of several control 
parameters. The display for auxiliary output 
viewing will be in engineering units for all but 
output. Output will be displayed in percent. 
ATTENTION Other prompts affected by 
these selections: 4mA VAL and 20mA VAL. 
ATTENTION Output cannot be configured 
when Three Position Step Control is used. 
 
 
DIS 
NO AUXILIARY OUTPUT 
 
 
IN1 
INPUT 1—This represents the configured 
range of input 1. 
FOR EXAMPLE: 
  Type J Thermocouple (0 °F to 1600 °F) 
  0 °F display = 0 % output 
  1600 °F display = 100 % output 
 
 
IN2 
INPUT 2 represents the value of the 
configured range of input 2. 
 
 
PROC 
PROCESS VARIABLE—Represents the 
value of the Process Variable. PV = Input 
XxRatioX + BiasX