Mitsubishi Electronics Q64TCTTN ユーザーズマニュアル
220
4.15
Auto-setting at Input Range Change
When the input range is changed, using this function automatically changes related buffer memory data to prevent an
error outside the setting range. Set the function on the "Switch Setting" window.
For details on the setting method, refer to the following.
error outside the setting range. Set the function on the "Switch Setting" window.
For details on the setting method, refer to the following.
The following is the setting timing.
(1) Buffer memory automatically set
Refer to
Common
Setting change instruction (YnB)
Buffer memory set automatically
Setting change completion flag (XnB)
Sampling cycle
Reflect
OFF
OFF
ON
ON
Before change
After change
User setting
Value changed
automatically
automatically
Reflects an output signal and buffer
memory values when the processing
starts by 500ms
memory values when the processing
starts by 500ms
After buffer memory values set automatically at the end
of the processing by 500ms are changed, turn on and
then off Setting change instruction (YnB).
of the processing by 500ms are changed, turn on and
then off Setting change instruction (YnB).
Reflect
CH Input range
(Un\G32, Un\G64, Un\G96, Un\G128)
500ms
500ms
500ms
Executed in a sequence program
Executed by the Q64TCN