CHAPTER 6 VARIOUS SETTINGS
6
6.2  Switch Settin
g
  
6.2
Switch Setting
Configure settings such as the output setting at CPU stop error and the control mode selection which are used in each 
channel.
(1) Setting method
Open the "Switch Setting" window.
Project window 
 [Intelligent Function Module]  
Module 
name  
[Switch 
Setting]
*1
Immediately after the control mode selection is changed, a set value discrepancy error (error code: 001E
H
) occurs. To 
clear the set value discrepancy error, turn off, on, and off E
2
PROM backup instruction (Yn8).
Item
Description
Set value
Reference
Output Setting at 
CPU Stop Error
Set whether to hold or clear the transistor output status 
when a CPU stop error occurs or when a CPU module is 
switched from RUN to STOP.
• 0: CLEAR (default value)
• 1:  HOLD
Control Mode 
Selection
*1
Set the control mode.
• 0: Standard Control
• 1: Heating/Cooling Control (Normal Mode)
• 2: Heating/Cooling Control (Expanded 
Mode)
• 3: Mix Control (Normal Mode)
• 4: Mix Control (Expanded Mode)
Auto-setting at 
Input Range 
Change
Set this item to change data of the related buffer 
memory automatically when the input range is changed 
so that an error which is out of the setting does not 
occur.
• 0: Disable
• 1: Enable
Setting Change 
Rate Limiter
Select "batch" setting or "individual" setting for the 
setting change rate limiter at temperature rise and drop .
• 0: Temperature Rise/Temperature Drop 
Batch Setting
• 1: Temperature Rise/Temperature Drop 
Individual Setting
Moving 
Averaging 
Process Setting
Set whether to enable or disable the moving averaging 
process.
• 0: Enable
• 1: Disable