Mitsubishi Electronics Q64TCTTN ユーザーズマニュアル

ページ / 430
375
APPENDICES
A
Appendix 2  Compar
ison of the
 Q64
T
CN w
ith th
e Q64
T
CT
T, Q64TC
T
T
B
W, Q64T
CRT,
 and 
Q64
T
CRT
BW
  
Appendix 2
Comparison of the Q64TCN with the 
Q64TCTT, Q64TCTTBW, Q64TCRT, and 
Q64TCRTBW
The Q64TCN has several new functions in addition to the functions of the Q64TCTT, Q64TCTTBW, Q64TCRT, and 
Q64TCRTBW (hereafter abbreviated as the Q64TC).
This section describes the comparison of functions, I/O signals, and buffer memory between the Q64TCN and Q64TC 
in accordance with the addition of the new functions. Precautions on replacing modules are also explained.
(1) Comparison of the functions between the Q64TCN and the Q64TC
The following table lists the functions supported by the Q64TCN and the Q64TC.
: Usable,  : Partially usable, ×: Unusable
Function
Q64TC
Q64TCN
Remarks
Control mode selection function
×
Control output setting at CPU stop 
error
Control method selection function
×
Manual reset function
×
Manual control
Auto tuning function
Simple two-degree-of-freedom
Derivative action selection function
×
Setting change rate limiter setting 
function
The temperature rise/temperature drop batch setting or individual setting 
can be selected on Switch Setting with the Q64TCN. (
Temperature process value (PV) 
scaling function
×
Moving averaging process to a 
temperature process value (PV)
×
Alert function
The reference set value (SV) for the deviation alert can be selected from 
among the following buffer memory areas with the Q64TCN. (
• CH Set value (SV) monitor (Un\G25 to Un\G28)
• CH Set value (SV) setting (Un\G34, Un\G66, Un\G98, Un\G130)
RFB limiter function
Sensor correction function
Errors can be corrected by setting any two points (corrected offset value 
and corrected gain value) with the Q64TCN. (
Auto-setting at input range change
×
Input/output (with another analog 
module) function
×
ON delay output function
Self-tuning function
×
Peak current suppression function
×
Simultaneous temperature rise 
function
×