Mitsubishi Electronics Q64TCTTN ユーザーズマニュアル

ページ / 430
403
APPENDICES
A
Appendix 5  On
line Module Chan
ge Pr
ocedure
 (When Using GX Wor
ks2)
Appendix 5.3  Operations of when 
perfor
m
ing a
n online mod
ule change
Appendix 5.3
Operations of when performing an online module 
change
The following table shows the operations of when performing an online module change.
: Executed ×: Not executed
*1
The access to the intelligent function module device (U\G) is included.
*2
The intelligent function module operates according to the previous setting when the user does not perform any 
operation.
(4) Check the operation.
(5) Restart the control.
Check the operation before the control starts.
(2) Remove the module.
Start the online module change 
using GX Works2.
Click the                   button on 
GX Works2 to enable 
the module to be removed.
Remove the selected module.
(3) Mount a new module.
Mount a new module.
After mounting the module, 
click                   on GX Works2.
Click the                   button on 
GX Works2 to turn off the online 
mode.
On "Modify Value     " on 
GX Works2, test the operation of
 the module after replacement.
Operation check is completed.
Restart the online module change 
using GX Works2. Click the 
                  button to restart 
the control.
The module is normally 
operating.
The operation of the module 
has stopped. 
   The RUN LED turns off.
The X/Y refresh restarts and 
the module starts up.
   The RUN LED turns on.
   Default operation 
  (Module READY flag (Xn0) 
  stays off.)
When there are initial 
setting parameters, the 
module starts to operate 
based on the initial setting 
parameters at this point.
The module operates based 
on the test operation*
1
.
Module READY flag (Xn0) 
turns on.
The module operates based on 
the initial setting sequence 
program started*
2
 when Module 
READY flag (Xn0) is started.
(1) Stop the operation.
Turn off all the Y signals turned 
on by the sequence program.
User operation
Operation of 
the Q64TCN
Operation of the CPU module
X/Y 
refresh
Device test
Initial setting 
parameters
FROM/TO 
instructions
*1