Mitsubishi Electronics AJ71E71N-B5T ユーザーズマニュアル

ページ / 6
 3 
 
[Function] 
(1) Data communication function (TCP/IP Communication and UDP/IP Communication) 
 
Communication Function 
Description 
QnA series 
A series 
Using read/write data in the PLC CPU  Reads/writes PLC CPU data from/to an external device.   
Procedure exist 
Using fixed 
buffers 
No Procedure 
Reads/writes any data between PLC CPU and an external device 
using fixed buffer of the Ethernet modules.   
Using random access buffers 
Exchanges data with multiple external devices, using the Ethernet 
random access buffers. (no need to specify external device)   
Using data link instructions 
Reads/writes PLC CPU data of other stations via the Ethernet 
using data link instructions.     
! N/A 
File transfer (FTP Server Function) 
Reads/writes files in the local station using the FTP server 
function, from an external device.   
! N/A 
 
(2) Other functions 
Function Description 
QnA 
series 
series 
MELSECNET/10 relay communication 
Data communication is enabled over a network system where 
Ethernet and MELSECNET/10 or multiple Ethernet networks are 
present.  
N/A 
Router relay communication (Router 
relay function) 
Communicates data via routers and gateways. (Ethernet module 
does not function as a router.)   
External device existence confirmation 
Checks whether or not the external device operates normally after 
communication has been established (open processing).   
Paring open communication 
Receiving connection and transmitting connection are opened as a 
single pair. (For fixed buffer communication.)   
Communication using automatic open 
UDP port 
Communication is enabled automatically after initial processing is 
completed of local station Ethernet module. (Opening and closing 
by a sequence program is unnecessary.)   
N/A 
Simultaneous broadcast 
Data is broadcasted simultaneously to all stations on the same 
Ethernet network where the Ethernet module is located. (Using 
UDP/IP)  
Access PLC CPU from GX Developer using Ethernet connection. 
 
Please refer to the new module's User's Manual for the function versions and serial numbers of the products 
!: Applicable 
        (CPU module and GX Developer) related to the above functions. 
 
[Performance Specifications] 
 
Specification 
AJ71QE71N-B5T 
A1SJ71QE71N-B5T 
AJ71QE71N-B2 
A1SJ71QE71N-B2 
AJ71E71N-B5T 
A1SJ71E71N-B5T 
AJ71E71N-B2 
A1SJ71E71N-B2 
Item 
10BASE5 10BASE-T 
10BASE2 
10BASE5 10BASE-T 
10BASE2 
Transmission speed 
10Mbps 
Transmission method   
Base band 
Maximum node-to-node 
distance 
2500m 
(8203ft.) 
- 925m 
(3035ft.) 
2500m 
(8203ft.) 
- 925m 
(3035ft.) 
Maximum segment 
length 
500m 
(1641ft.) 
100m  
(323ft.) (*1) 
185m (607ft.) 
500m 
(1641ft.) 
100m 
(323ft.) (*1) 
185m (607ft.) 
Maximum number of 
nodes per connection 
100 units/ 
segment 
Cascade 
connection, 
maximum 4 
30 units/ segment 
100 units/ 
segment 
Cascade 
connection, 
maximum 4 
30 units/ 
segment 
Transmission 
Specifications 
Minimum node interval 
2.5m (8.2ft.) 
0.5m (1.6ft.) 
2.5m (8.2ft.) 
0.5m (1.6ft.) 
Number of 
simultaneously open 
connections allowed 
8 connections (Connections usable by the sequence program) 
Fixed buffer 
1k words 
×
 8 
1k words 
×
 8 
Send/receive 
data storage 
memory 
Random access buffer 
6k words 
×
 1 
3k words 
×
 2 
Number of occupied I/O points   
32 points   
5VDC current consumption 
AJ71QE71N-B5T  :0.48A 
AJ71QE71N-B2   :0.56A 
A1SJ71QE71N-B5T:0.42A 
A1SJ71QE71N-B2 :0.64A 
AJ71E71N-B5T  :0.48A 
AJ71E71N-B2   :0.56A 
A1SJ71E71N-B5T:0.42A 
A1SJ71E71N-B2 :0.64A 
12VDC external supply power capacity 
(for transceiver) 
(*2)  (*2) 
 
*1 Between hub and node. 
*2 It is necessary to use a power supply that meets the specifications of the transceiver and AUI cable, considering the voltage drop 
(maximum 0.80V) in the module.