Mitsubishi Electronics Q64TCRTN ユーザーズマニュアル

ページ / 430
220
4.15
Auto-setting at Input Range Change 
When the input range is changed, using this function automatically changes related buffer memory data to prevent an 
error outside the setting range. Set the function on the "Switch Setting" window.
For details on the setting method, refer to the following.
The following is the setting timing.
(1) Buffer memory automatically set
Refer to 
Common
Setting change instruction (YnB)
Buffer memory set automatically
Setting change completion flag (XnB)
Sampling cycle
Reflect
OFF
OFF
ON
ON
Before change
After change
User setting
Value changed 
automatically
Reflects an output signal and buffer 
memory values when the processing 
starts by 500ms
After buffer memory values set automatically at the end 
of the processing by 500ms are changed, turn on and 
then off Setting change instruction (YnB).
Reflect
CH    Input range 
(Un\G32, Un\G64, Un\G96, Un\G128)
500ms
500ms
500ms
Executed in a sequence program
Executed by the Q64TCN