Mitsubishi Electronics Q64TCRTN ユーザーズマニュアル

ページ / 430
287
CHAPTER 5 SETTINGS AND THE PROCEDURE BEFORE OPERATION
5
5.4  Wiring
5.4.1  Wiring pr
ecautions
5.4
Wiring
This section describes the wiring precautions and module connection examples.
5.4.1
Wiring precautions
External wiring that is less likely to be affected by noise is one of the conditions for a highly reliable system that fully 
utilizes the Q64TCN.
This section describes wiring precautions.
 • Use separate cables for the AC control circuit and the Q64TCN's external I/O signals to avoid influence of 
AC side surges and induction.
 • Do not locate external wires near the main circuit line, high-voltage circuit lines, and load circuit lines of 
devices other than programmable controllers such as an inverter. Also, do not bunch external wires with 
these lines. Otherwise, the external wires are more likely to be affected by noise, surges, and induction. 
 • Ground shielded cables at one end on the programmable controller side. However, depending on the 
external noise condition, it should be grounded on the other side.
 • To ensure that this product maintains EMC and Low Voltage Directives, please refer to the manual included 
with the CPU module or base unit.