Motorola MCF5282 ユーザーズマニュアル

ページ / 816
25-6
MCF5282 User’s Manual
MOTOROLA
 
Message Buffers  
Table 25-2. Common Extended/Standard Format Frames
Field
Description
Time Stamp Contains a copy of the high byte of the free running timer, which is captured at the beginning of the 
identifier field of the frame on the CAN bus.
Code
Rx Length
Length (in bytes) of the Rx data stored in offset 0x6 through 0xD of the buffer. This field is written by 
the FlexCAN module, copied from the data length code (DLC) field of the received frame.
Tx Length
Length (in bytes) of the data to be transmitted, located in offset 0x6 through 0xD of the buffer. This 
field is written by the CPU, and is used as the DLC field value. If remote transmission request (RTR)) 
= 1, the frame is a remote frame and will be transmitted without the data field, regardless of the value 
in Tx length.
Data
This field can store up to eight data bytes for a frame. For Rx frames, the data is stored as it is 
received from the bus. For Tx frames, the CPU provides the data to be transmitted within the frame.
Reserved
This word entry field (16 bits) should not be accessed by the CPU.
Table 25-3. Message Buffer Codes for Receive Buffers
Rx Code 
Before Rx 
New Frame
Description
Rx Code 
After Rx 
New Frame
Comment
0000
NOT ACTIVE — message buffer is not active.
0100
EMPTY — message buffer is active and empty.
0010
0010
FULL — message buffer is full.
0110
If a CPU read occurs before 
the new frame, new receive 
code is 0010.
0110
OVERRUN — second frame was received into a full 
buffer before the CPU read the first one.
0101
 1
1
For transmit message buffers, upon read, the BUSY bit should be ignored.
BUSY — message buffer is now being filled with a new 
receive frame. This condition will be cleared within 20 
cycles.
0010
An empty buffer was filled.
0011
1
0110
A full buffer was filled.
0111
1
0110
An overrun buffer was filled.
Table 25-4. Message Buffer Codes for Transmit Buffers
RTR
Initial Tx Code
Description
Code After 
Successful 
Transmission
X
1000
Message buffer not ready for transmit.
0
1100
Data frame to be transmitted once, unconditionally.
1000
1
1100
Remote frame to be transmitted once, and message buffer 
becomes an Rx message buffer for data frames.
0100
0
1010
 1
1
When a matching remote request frame is detected, the code for such a message buffer is changed to be 1110.
Data frame to be transmitted only as a response to a remote 
frame.
1010
0
1110
Data frame to be transmitted only once, unconditionally, and 
then only as a response to remote frame.
1010