Calibration Menu and the KCTSTP/KCTRD Commands
 ION 7500 / ION 7600 User’s Guide
Page 188
Current Probe Inputs Basic Setup Technical Note
Calibration Menu and the KCTSTP/KCTRD Commands
The Calibration menu lets you access setup registers in the meter Factory module. 
With the read/write commands KCTRD and KCTSTP, you can program the meter 
with parameters appropriate for your current probes. 
Calibration Menu and Help   
The Calibration menu contains the following calibration commands:
Description of KCTSTP and KCTRD Calibration Commands   
The command KCTSTP writes all current probe setup registers. The command 
KCTRD reads all current probe setup registers.
KCTSTP <tag> <I> <V> <phase angle> <u> <ch>
Write the external current probe setup registers
Description:
This command writes to non-volatile registers containing the external current 
probe parameters
Arguments:
<tag> the current probe model or name tag, maximum of 15 characters; do not 
leave spaces
 between characters
<I> the RMS value of the nominal primary current of the current probe
<V> the nominal RMS value of the secondary nominal voltage of the current probe
<phase angle> current probe’s phase angle in degrees for constant phase 
compensation
<u> selected register group: 1-User Defined 1, 2-User Defined 2
<ch> selected current channel(s): 4-6 (4=I1;5=I2;6=I3), 44 (44 = ALL PHASE 
CURRENT CHANNELS: I1,I2,I3) 
TERMINAL COMMANDS
KRD
Read All RMS Calibration Constants
KFRD
Read All Force Levels
KFSRD
Read All Full Scale Values
KCTSTP <tag> <I> <V> <phase angle> <u> <ch>
Write Setup for External CT
KCTRD
Read Setup of External CTs
KD
Read Power Meter Module Diagnostics