Multi-Tech Systems 7500 ユーザーズマニュアル
Calibration Menu and the KCTSTP/KCTRD Commands
ION 7500 / ION 7600 User’s Guide
Page 188
Current Probe Inputs Basic Setup Technical Note
Calibration Menu and the KCTSTP/KCTRD Commands
The Calibration menu lets you access setup registers in the meter Factory module.
With the read/write commands KCTRD and KCTSTP, you can program the meter
with parameters appropriate for your current probes.
With the read/write commands KCTRD and KCTSTP, you can program the meter
with parameters appropriate for your current probes.
Calibration Menu and Help
The Calibration menu contains the following calibration commands:
Description of KCTSTP and KCTRD Calibration Commands
The command KCTSTP writes all current probe setup registers. The command
KCTRD reads all current probe setup registers.
KCTRD reads all current probe setup registers.
KCTSTP <tag> <I> <V> <phase angle> <u> <ch>
Write the external current probe setup registers
Description:
This command writes to non-volatile registers containing the external current
probe parameters
This command writes to non-volatile registers containing the external current
probe parameters
Arguments:
<tag> the current probe model or name tag, maximum of 15 characters; do not
leave spaces between characters
<tag> the current probe model or name tag, maximum of 15 characters; do not
leave spaces between characters
<I> the RMS value of the nominal primary current of the current probe
<V> the nominal RMS value of the secondary nominal voltage of the current probe
<phase angle> current probe’s phase angle in degrees for constant phase
compensation
compensation
<u> selected register group: 1-User Defined 1, 2-User Defined 2
<ch> selected current channel(s): 4-6 (4=I1;5=I2;6=I3), 44 (44 = ALL PHASE
CURRENT CHANNELS: I1,I2,I3)
CURRENT CHANNELS: I1,I2,I3)
TERMINAL COMMANDS
KRD
Read All RMS Calibration Constants
KFRD
Read All Force Levels
KFSRD
Read All Full Scale Values
KCTSTP <tag> <I> <V> <phase angle> <u> <ch>
Write Setup for External CT
KCTRD
Read Setup of External CTs
KD
Read Power Meter Module Diagnostics