Multi-Tech Systems 7500 ユーザーズマニュアル

ページ / 372
Detailed Module Operation
 ION 7500 / ION 7600 User’s Guide
Page 222
Digital and Analog I/O Technical Note
Maximum State
In P
ULSE
 mode during maximum operation, the Source input increases so the on-
time and off-time of the pulses are equal. 
The diagram above shows seven complete pulses for the Calibration Pulser 
module in P
ULSE
 mode, and fourteen transitions for the Calibration Pulser module 
in KYZ mode.  If the Kt register was set up to send a pulse or KYZ transition for 1.8 
energy-hours on each module respectively, then the module in KYZ mode has 
output twice as much energy-hours than the module in P
ULSE
 mode.   
Overload State
If the Source input increases so that an excessive number of state changes appear at 
the hardware channel, the Overload Boolean output is turned 
ON
, and pulsing stops 
(i.e. the LED or digital output will remain on) until the energy values return to a 
nominal level. The Overload Boolean output is available for Calibration Pulser 
modules in P
ULSE
 or KYZ mode. 
The diagram above shows three complete pulses for the Calibration Pulser module 
in P
ULSE
 mode, and six transitions for the Calibration Pulser module in KYZ mode. 
For both modules, the Overload output has turned on, causing the LED to remain 
lit. 
Pulse mode
Pulse Width
(e.g. duration of a lit LED)
Time
KYZ mode
High-Low
transitions
Time
Pulse Width
(e.g. duration of a lit LED)
Excessive transitions (overload
state) causes the LED
to remain lit
Excessive pulsing (overload
state) causes the LED
to remain lit
Pulse mode
KYZ mode
High-Low
transitions