Multi-Tech Systems 7500 ユーザーズマニュアル

ページ / 372
Magnitude of Voltage Supply
 ION 7500 / ION 7600 User’s Guide
Page 306
Power Quality: ION Meters and EN50160 Technical Note
Optionally, the data below can be recorded every 10 minutes by Data Recorder 32:
Parameter
Description
PQ V1 mean
average voltage on phase 1 over 10 minutes
PQ V1 low
minimum voltage on phase 1 over 10 minutes (HS measurement) 
PQ V1 high
maximum voltage on phase 1 over 10 minutes (HS measurement) 
PQ V2 mean
average voltage on phase 2 over 10 minutes
PQ V2 low
minimum voltage on phase 2 over 10 minutes (HS measurement) 
PQ V2 high
maximum voltage on phase 2 over 10 minutes (HS measurement) 
PQ V3 mean
average voltage on phase 3 over 10 minutes
PQ V3 low
minimum voltage on phase 3 over 10 minutes (HS measurement) 
PQ V3 high
maximum voltage on phase 3 over 10 minutes (HS measurement)