Temporary Overvoltages
 ION 7500 / ION 7600 User’s Guide
Page 314
Power Quality: ION Meters and EN50160 Technical Note
The following counters are from the Previous Observation period (PO). These 
values are all located in Store modules.
The Maximum module output registers are used for display purposes:
Optionally, the data below can be recorded at the end of every Overvoltage event 
by Data Recorder 36.
V3-Ovrvlt N11
 V3-Ovrvlt N12
 V3-Ovrvlt N13
 V3-Ovrvlt N14
 V3-Ovrvlt N15
V3-Ovrvlt N21
 V3-Ovrvlt N22
 V3-Ovrvlt N23
 V3-Ovrvlt N24
 V3-Ovrvlt N25
V3-Ovrvlt N31
 V3-Ovrvlt N32
 V3-Ovrvlt N33
 V3-Ovrvlt N34
 V3-Ovrvlt N35
Register Labels
PO V1-Ovrvlt 
N11
 PO V1-Ovrvlt N12  PO V1-Ovrvlt N13  PO V1-Ovrvlt N14  PO V1-Ovrvlt 
N15
PO V1-Ovrvlt 
N21
 PO V1-Ovrvlt N22  PO V1-Ovrvlt N23  PO V1-Ovrvlt N24  PO V1-Ovrvlt 
N25
PO V1-Ovrvlt 
N31
 PO V1-Ovrvlt N32  PO V1-Ovrvlt N33  PO V1-Ovrvlt N34  PO V1-Ovrvlt 
N35
PO V2-Ovrvlt 
N11
 PO V2-Ovrvlt N12  PO V2-Ovrvlt N13  PO V2-Ovrvlt N14  PO V2-Ovrvlt 
N15
PO V2-Ovrvlt 
N21
 PO V2-Ovrvlt N22  PO V2-Ovrvlt N23  PO V2-Ovrvlt N24  PO V2-Ovrvlt 
N25
PO V2-Ovrvlt 
N31
 PO V2-Ovrvlt N32  PO V2-Ovrvlt N33  PO V2-Ovrvlt N34  PO V2-Ovrvlt 
N35
PO V3-Ovrvlt 
N11
 PO V3-Ovrvlt N12  PO V3-Ovrvlt N13  PO V3-Ovrvlt N14  PO V3-Ovrvlt 
N15
PO V3-Ovrvlt 
N21
 PO V3-Ovrvlt N22  PO V3-Ovrvlt N23  PO V3-Ovrvlt N24  PO V3-Ovrvlt 
N25
PO V3-Ovrvlt 
N31
 PO V3-Ovrvlt N32  PO V3-Ovrvlt N33  PO V3-Ovrvlt N34  PO V3-Ovrvlt 
N35
Register Label
Description
V1-Ovrvlt mx
greatest over-voltage on phase 1 over 1 week
V2-Ovrvlt mx
greatest over-voltage on phase 2 over 1 week
V3-Ovrvlt mx
greatest over-voltage on phase 3 over 1 week
Register Label
Description
V1-Ovrvlt [%]
over-voltage on phase 1
V2-Ovrvlt [%]
over-voltage on phase 2
V3-Ovrvlt [%]
over-voltage on phase 3
V1-Ovrvlt durtn
over-voltage duration on phase 1
V2-Ovrvlt durtn
over-voltage duration on phase 2
V3-Ovrvlt durtn
over-voltage duration on phase 3
Register Labels