Customizing the Modbus Master Framework
 ION 7500 / ION 7600 User’s Guide
Page 328
Sub-Metering with a Modbus Master Technical Note
Customizing the Modbus Master Framework
The Modbus Master framework is designed to handle 12 Modbus Slave devices. 
This is limited by the number of Modbus Import Modules supported by ION 
meters. Each Modbus Slave device uses five Modbus Import Modules, two 
Arithmetic Modules, and two Data Recorder Modules. If you do not require all 12 
Modbus Slaves, you may want to remove some the extra Sub Meter folders from 
your framework. Deleting unused Sub Meter folders will free unused resources 
on your meter. 
Once all unused Sub Meter folders have been deleted, verify that the Unit IDs in 
each Sub Meter folder of your framework corresponds to the Unit IDs of the 
meters on your Modbus Network. To verify Unit IDs, right-click on each Modbus 
Import Module
 in a Sub Meter folder and verify the value in the Device Name 
setup register corresponds to the Unit ID of your meter. 
Multiple Modbus Master Devices
After you have pasted and customized the Modbus Master framework into one of 
your meters, you can then use this framework to paste into the other Modbus 
Master meters in your site.  The following procedure describe how to copy the 
Modbus Master framework into several Modbus Master meters.  Follow the  steps 
outlined below to ensure framework consistency across each meter in your site.  
1.
After you have customized your Modbus Master framework (see previous 
section), select the Modbus Master Framework folder from the Advanced 
Configuration
 folder
2.
Select Edit>Copy to framework.
3.
Type a descriptive name for your custom framework.  Click Save.
4.
Connect to the next meter you would like to paste your custom framework into.
5.
Double-click the Frameworks folder to access the meter’s Advanced 
Configuration
 folder.
6.
Select Edit>Paste from Framework.
7.
In the Paste Summary dialog box, click the green checkmark to the left of the 
first  module in the list.  Hold down your keyboard’s Shift key and click the last 
module in the list.  The checkmark changes to a checkmark and a lock icon.  This 
lets you “lock paste” the modules into your meter. 
N
OTE
When pasting your customized Modbus Master framework, it is important to “lock paste” the modules
into the meter so that all the Modbus Master meters have identical frameworks.  This is particularly
important when creating Vista diagrams that are compatible across the different Modbus Master meters. 
8.
Click OK.  When the pasting is completed, a new folder called Modbus Master 
Framework
 appears.