ION 7500 / ION 7600 User’s Guide
Step 3: Configure the ION Gateway Meter for ModemGate
The ION Meter as a ModemGate Technical Note
Page 345
Step 3: Configure the ION Gateway Meter for ModemGate
You need to configure the communications settings on the ION meter that serves 
as a gateway. 
1.
Once the gateway meter is installed and the internal modem is connected, use 
the front panel of the meter to configure the internal modem and the serial 
communications port. 
2.
Set the internal modem baud rate, Unit ID and protocol (for most applications 
the default settings are appropriate). The baud rate must be the same for the port 
hosting the gateway and all connected devices.
3.
Set the protocol (on the meter) for the port hosting the gateway to 
MODEMGATE
If you have an ION 7300 Series meter select 
ION
 as the protocol. The baud rate 
for this port must be the same as all other communicating ports.
N
OTE
You cannot have 
MODEMGATE
  (
ION
 on the ION 7300 Series meter) protocol enabled on two ports
simultaneously.