Multi-Tech Systems 7500 ユーザーズマニュアル

ページ / 372
ION 7500 / ION 7600 User’s Guide
Data Logging Setup
Chapter 3 - Default Meter Functionality 
Page 55
Historic Data Logging
Three data recorders are used to record “standard” power system quantities, such 
as phase current, phase voltage and power factor. These recorders are labeled Hist 
Mean Log
Hist High Log, and Hist Low Log. By default, they log the following ION 
output register values:
Loss Log
The Loss Log recorder is configured to record loss values. By default, it logs the 
following ION parameters:
Harmonics Logging
Two recorders provide various harmonics logs, including K-factor and Total 
Harmonics Distortion (THD). These recorders are labeled Harm Mean Log and 
Harm High Log. By default, they log the following ION output register values:
Hist Mean Log
Hist High Log
Hist Low Log
Vll ab mean
I avg mean
Vll ab high
I avg high
Vll ab low
I avg low
Vll bc mean
I 4 mean
Vll bc high
I 4 high
Vll bc low
I 4 low
Vll ca mean
kW tot mean
Vll ca high
kW tot high
Vll ca low
kW tot low
Vll avg mean
kVAR tot mean
Vll avg high
kVAR tot high
Vll avg low
kVAR tot low
V unbal mean
kVA tot mean
V unbal high
kVA tot high
V unbal low
kVA tot low
Ia mean
PF lag mean
Ia high
PF lag high
Ia low
PF lag low
Ib mean
PF lead mean
Ib high
PF lead high
Ib low
PF lead low
Ic mean
Freq mean
Ic high
Freq high
Ic low
Freq low
Parameter
Description
MU Ia^2h int
Phase A interval current squared hours
MU Ib^2h int
Phase B interval current squared hours
MU Ic^2h int
Phase C interval current squared hours
MU Vll ab^2h int
Phase A interval voltage Line-to-Line squared hours
MU Vll bc^2h int
Phase B interval voltage Line-to-Line squared hours
MU Vll ca^2h int
Phase C interval voltage Line-to-Line squared hours
Harm Mean Log
Harm High Log
V1 THD mean
I1 K Fac mean
V1 THD high
I1 K Fac high
V2 THD mean
I2 K Fac mean
V2 THD high
I2 K Fac high
V3 THD mean
I3 K Fac mean
V3 THD high
I3 K Fac high
I1 THD mean
I1 THD high
I2 THD mean
I2 THD high
I3 THD mean
I3 THD high