Energy Pulsing Setup
 ION 7500 / ION 7600 User’s Guide
Page 58
Chapter 3 - Default Meter Functionality 
Energy Pulsing Setup
Each meter has both the Calibration Pulser module and the Pulser module.
Pulser Module Settings
The Pulser module serves as an intermediary between other modules’ pulse 
output registers (accepting them as pulse inputs) and a hardware output channel 
on the device. These modules are capable of sending pulses or pulse transitions to 
any hardware output channel. The Pulser module contains the following setup 
registers:
Five common parameters (kWh del, kWh rec, kVARh del, kVARh rec, and kW sd 
del) are already linked to the Pulser modules for you.
N
OTE
For safety reasons, no hardware channel has been  selected.  To  make  use  of  these  links,  you  must
configure the Pulser modules’ 
Port
 setup registers to the appropriate hardware port that receives the 
output.
Calibration Pulser Module Settings
The Calibration Pulser module is a highly accurate energy pulser used for 
verifying calibration on meters employed in billing applications. This module type 
serves as an intermediary between the power (kW, kVAR or kVA) outputs of the 
Power Meter module and a device’s hardware output channel.
The setup registers of the module labeled “kWh Pulser –D4,” allow you to 
configure the solid-state output D4 for calibration pulsing. By default, the output 
on a standard meter generates a pulse for every 1.8Wh accumulated. This is the 
same pulsing rate as the middle front panel LED (controlled by a Calibration 
Pulser module labeled “kWh Pulser –LED”). You can modify the pulsing rate of 
either channel by changing the value of the Kt setup register of the controlling 
Calibration Pulser module (see below).
Setup 
Register
Function
Default
Pulse Width
This numeric bounded register specifies the width, in seconds, 
of the output pulses.
1
OutputMode
This register defines whether the output is a complete pulse or 
a transition pulse (KYZ).
Pulse
Polarity
This register specifies the polarity of output. It has no effect if 
OutputMode 
is KYZ.
Non-inverting
Port
This register specifies which hardware port the output appears 
on. Only those hardware channels that are still available 
appear when you access this setting.
Not Used