ION 7500 / ION 7600 User’s Guide
COM1 Port
Chapter 6 - Hardware Reference 
Page 165
External Modem Connections 
RS-485 Connections
RS-485 connections are made via the captured-wire connectors on the rear of the meter. 
Devices can be connected in series using RS-485 (see diagram to the left). Be sure not to 
ground the wires at both ends.
Specifications are as follows:
Connections
1
The lengths of all (+ and –) cable segments must be counted including those that connect devices to 
terminal blocks. 
Terminal connections on the meter are marked as follows:
Specification
Description
Cable Type
Standard straight-through RS-232 cable
Cable Ends
DB9 female end for mating with the DB9 male connector on the meter
Max. Cable Length
50 feet (15.2 m)
Specification
Value
Baud Rates
300 to 57,600 bps (default is 9,600 bps)
Duplex
Half
Supported Protocols
ION, Modbus RTU, DNP 3.0, FACTORY, Iec870-102, GPS: Arbiter,
GPS: TRUE TIME DATUM, EtherGate, ModemGate (default is ION)
Isolation
Optical isolation from all other inputs and outputs (the COM1 RS-485 port 
is not isolated from the COM1 RS-232 port); isolation voltage is 750 V 
peak for 10 seconds @ 60 Hz.
Specification
Description
Cable Type
Good quality shielded twisted pair cable, AWG 22 or larger. 
Max. Cable Length
4,000 ft. (1219 m) 
1
Max. number of 
devices per bus
32
Marking
Terminal Function
SHLD
RS-485 Shield
RS-485 Data Minus
+
RS-485 Data Plus
SH + -
SH
COM
RS-485
+
-