Multi-Tech Systems 7600 ユーザーズマニュアル

ページ / 372
ION 7500 / ION 7600 User’s Guide
I/O Specifications
Chapter 6 - Hardware Reference 
Page 171
N
OTE
Because mechanical relays have limited lifetimes, mechanical KYZ relays are typically not suitable for
energy pulsing applications. For energy pulsing applications, consider using Form A outputs in KYZ
mode.
A typical connection and operational details are illustrated below.. 
N
OTE
The mechanical relays should be protected by external fuses.
Solid-State Relay Outputs
Specifications for the four digital relay (Form A) outputs (D1 through D4) are as 
follows:
1
Digital output D4 is configured at the factory to emit pulses for calibration testing purposes.
Operational Block Diagram
STATE
RX1 – RX2
RX2 – RX3
Inactive
Open
Closed
Active
Closed
Open
Pulse
Closed for 
duration of pulse
Open for duration 
of pulse
R
X1
R
X2
R
X3
N/O
N/C
R
11
R
12
R
13
R
21
R
22
R
23
R
31
R
32
R
33
Specification
Value
Signal Type
Continuous or pulse 
1
Maximum Load Voltage
30V
Maximum Load Current
80 mA
Isolation
5,000 Vrms
Scan Time
½ cycle
Connection Type
Captured-wire
Wire Type
AWG 28 to AWG 16
Rear View of Meter
Standard I/O 
Solid-State relays