Multi-Tech Systems 7600 ユーザーズマニュアル

ページ / 372
ION 7500 / ION 7600 User’s Guide
Electrical Specifications
Chapter 6 - Hardware Reference 
Page 175
Current Inputs
Specification
5A Option
1A Option
Input Rating
5A, 10A, or 20A
1A, 2A, 5A, or 10A
Fault Capture
70A peak
17.5A peak
Maximum Voltage
600V RMS (CAT III IEC61010-1)
600V RMS (CAT III IEC61010-1)
Impedance
2 mΩ
15 mΩ
Burden
0.05 VA per phase (at 5A)
0.015 VA per phase (at 1A)
Dielectric Withstand
3250 VAC, 60Hz for 1 minute
3250 VAC, 60Hz for 1 minute
Overload
500A RMS for 1 second, non-
recurring
50A RMS for 1 second, non-
recurring