ION 7500 / ION 7600 User’s Guide
Setpoint Configuration
Chapter 3 - Default Meter Functionality 
Page 61
Setpoint Configuration
The Relative Setpoint module provides extensive control, secondary protection, 
and analysis capabilities by allowing you to initiate an action in response to a 
specific condition. It is particularly useful for performing actions based on 
differences between a value (e.g. kW on phase A) relative to a reference value (e.g. 
kW demand for all three phases). You can use this module’s outputs for demand 
control of equipment or any other applications requiring setpoint activity relative 
to a varying value.
The Relative Setpoint modules monitor the following for "over" conditions: phase 
current, kW demand, and voltage unbalance. 
Relative Setpoint Module Settings
There is no need to change any of the Relative Setpoint modules’ setup registers 
for normal operation of the meter.
Fine Tuning Over Condition Monitoring
If you want to fine-tune over condition monitoring, the only setup registers you 
should change are SusUntlON and SusUntlOFF
SusUntlON determines how long the modules wait after an over condition is 
detected before reporting it. This gives the monitored value a short period to 
correct itself before the event is registered with the module so that very brief over 
conditions are ignored. Similarly, SusUntlOFF is the amount of time a normal 
value must be present before the module considers normal operation to be 
restored. Both SusUntlON and SusUntlOFF values are entered in seconds (the 
default value for both is 30 seconds).
Refer to the online ION Programmer’s Reference for more information about the 
Relative Setpoint module.
Module
Label
Description
Relative Setpoint 1
Over KW sd
When active, this annunciates when the total kW SWDemand exceeds a specified amount.
Relative Setpoint 2
Over I a
When active, this annunciates when the current on phase A exceeds a specified amount.
Relative Setpoint 3
Over I b
When active, this annunciates when the current on phase B exceeds a specified amount.
Relative Setpoint 4
Over I c
When active, this annunciates when the current on phase C exceeds a specified amount.
Relative Setpoint 5
Over V unbal
When active, this annunciates if the voltage unbalance exceeds a specified percentage.
Relative Setpoint 6
Over I 4
When active, this annunciates when I 4 exceeds a specified amount.
Relative Setpoint 7
Over I 5
When active, this annunciates when I 5 exceeds a specified amount.