Command Interface
5-20
SIMATIC NET CP 243-2 AS-i Master
C79000-G8976-C142/02
5.2.8
Store_Actual_Configuration
Purpose of the Command
With this call, the (actual) configuration data (I/O configuration, ID code, extended
ID1 code and extended ID2 code) of all AS-i slaves are stored permanently in the
EEPROM as the (expected) configuration data. The list of activated AS-i slaves
(LAS) is adopted in the list of permanent AS-i slaves (LPS).
ID1 code and extended ID2 code) of all AS-i slaves are stored permanently in the
EEPROM as the (expected) configuration data. The list of activated AS-i slaves
(LAS) is adopted in the list of permanent AS-i slaves (LPS).
When this command is executed, the AS-i master changes to the offline phase and
then changes back to the normal mode (warm restart on the AS-i master).
then changes back to the normal mode (warm restart on the AS-i master).
The call is not executed in the protected mode.
Structure of the Job Data in the Send Buffer
Bank
Byte
Meaning
2
0
Command number: 07
H
Structure of the Job Data in the Receive Buffer
Bank
Byte
Meaning
2
0
Echo of the command number: 07
H
2
1
Command status