RuggedCom RX1000 ユーザーズマニュアル

ページ / 284
Chapter 20 – Configuring GOOSE Tunnels
Chapter 20 – Configuring GOOSE Tunnels
Introduction
This chapter familiarizes the user with:
Configuring GOOSE Tunnels
Viewing GOOSE Tunnel status and statistics
Tracing GOOSE activity 
IEC61850 GOOSE Fundamentals
IEC61850 is an international standard for substation automation.   It is a part of the 
International Electrotechnical Commission’s (IEC) Technical Committee 57 (TC57) 
architecture for electric power systems.
One feature of IEC61850 is the fast transfer of events.  Transfers of Generic 
Substation Events (GSEs) are accomplished through the GOOSE (Generic Object 
Oriented Substation Event) protocol.  
IEC61850 uses Layer 2 multicast frames to distribute its messages and hence, is 
incapable of operating outside of a switched Ethernet Network.  The GOOSE tunnel 
feature provides a capability to bridge GOOSE frames over a WAN.
GOOSE tunnels provides you with the following features:
GOOSE traffic is bridged over the WAN via UDP packets. 
One GOOSE traffic source can be mapped to multiple remote router 
Ethernet interfaces in mesh fashion.
To reduce bandwidth consumption, GOOSE daemons may be located at 
each of the “legs” and at the center of a star network.  The centrally 
located daemon will accept GOOSE packets and re-distribute them. 
Statistics reports availability of remote GOOSE daemons, packet counts 
and Round Trip Time (RTT) for each remote daemon. 
When Virtual Router Redundancy Protocol (VRRP) is employed, GOOSE 
transport is improved by sending redundant GOOSE packets from each VRRP 
gateway. 
Layer 2 Tunnel Daemon Details
The GOOSE protocol is supported by the Layer 2 Tunnel Daemon.  The daemon 
listens to configured Ethernet interfaces and to the network itself upon a configurable 
UDP port.
The Media Access Control (MAC) destination address of frames received from 
Ethernet is inspected in order to determine which GOOSE group they are in.  The 
frames are then encapsulated in network headers and forwarded (with MAC source 
and destination addresses intact) to the network as GOOSE packets.
IEC61850 recommends that the MAC destination address should be in the range 
01:0c:cd:01:00:00 to  01:0c:cd:01:01:ff.
RuggedCom                                                                                                                                      195