IBM 520Q ユーザーズマニュアル

ページ / 110
Chapter 1. General description 
15
򐂰
Width:   605 mm (23.8 in.) with side panels
򐂰
Depth: 1001 mm (39.4 in.) with front door
򐂰
Height: 1344 mm (49.0 in.)
򐂰
Weight: 100.2 kg (221.0 lb.)
The S25 rack has a maximum load limit of 22.7 kg (50 lb.) per EIA unit for a maximum loaded 
rack weight of 667 kg (1470 lb.).
1.5.5  S11 rack and S25 rack considerations
The S11 and S25 racks do not have vertical mounting space that will accommodate FC 7188 
PDUs. All PDUs required for application in these racks must be installed horizontally in the 
rear of the rack. Each horizontally mounted PDU occupies 1U of space in the rack, and 
therefore reduces the space available for mounting servers and other components. 
FC 0469 Customer Specified Rack Placement provides the ability to specify the physical 
location of the system modules and attached expansion modules (drawers) in the racks. The 
client’s request is reviewed by eConfig for safe handling by checking the weight distribution 
within the rack. The Manufacturing Plant provides the final approval for the configuration. This 
information is then used by IBM Manufacturing to assemble the system components 
(drawers) in the rack according to the client’s request. 
The CFReport from eConfig must be submitted to the following site: 
 
Table 1-11 on page 16 lists the machine types that are supported in the S11 and S25 racks.