Mitsubishi Electronics QD75MH2 ユーザーズマニュアル

ページ / 838
 
 
 
5 - 78 
MELSEC-Q
 
5   DATA USED FOR POSITIONING CONTROL 
 
 
 
 
 
Item  2 Setting 
details 
Setting value 
 
Pr.147  
(PB29) 
Gain changing ratio of load 
inertia moment to 
servomotor inertia moment 
• Used to set the ratio of load inertia moment to servo 
motor inertia moment when gain changing is valid. 
• This parameter is made valid when the auto tuning is 
invalid (" Pr.108  Auto tuning mode" : 3). 
0.0 to 300.0[Times] 
 
 
 
 
Pr.148  
(PB30) 
Gain changing position loop 
gain 
• Set the position loop gain when the gain changing is 
valid. 
• This parameter is made valid when the auto tuning is 
invalid (" Pr.108  Auto tuning mode" : 3). 
1 to 2000[rad/s] 
 
 
 
 
Pr.149  
(PB31) 
Gain changing speed loop 
gain 
• Set the speed loop gain when the gain changing is 
valid. 
• This parameter is made valid when the auto tuning is 
invalid (" Pr.108  Auto tuning mode" : 3). 
20 to 50000[rad/s] 
 
 
 
 
Pr.150  
(PB32) 
Gain changing speed 
integral compensation 
• Set the speed integral compensation when the gain 
changing is valid.  
• This parameter is made valid when the auto tuning is 
invalid (" Pr.108  Auto tuning mode" : 3). 
0.1 to 5000.0[ms] 
 
 
 
 
Pr.151  
(PB33) 
Gain changing vibration 
suppression control vibration 
frequency setting 
• Set the vibration frequency for vibration suppression 
control when the gain changing is valid.  
• This parameter is made valid when " Pr.120  
Vibration suppression control filter tuning mode" 
setting is "2: Manual mode" and " Pr.144  Gain 
changing selection " setting is "1: "Cd.108 Gain 
changing command" (setting value) is valid". 
Note): When using the vibration suppression control 
gain changing, always execute the changing 
after the servomotor has stopped. 
0.1 to 100.0[Hz] 
 
 
 
 
 
 
 
 
 
 
 
Gain
• filte
r se
ttin
Pr.152  
(PB34) 
Gain changing vibration 
suppression control 
resonance frequency setting 
• Set the resonance frequency for vibration 
suppression control when the gain changing is valid.  
• This parameter is made valid when " Pr.120  
Vibration suppression control filter tuning mode" 
setting is "2: Manual mode" and " Pr.144  Gain 
changing selection " setting is "1: "Cd.108 Gain 
changing command" (setting value) is valid". 
Note): When using the vibration suppression control 
gain changing, always execute the changing 
after the servomotor has stopped. 
0.1 to 100.0[Hz]