Mitsubishi Electronics QD75MH2 ユーザーズマニュアル

ページ / 838
 
 
 
12 - 72 
MELSEC-Q
 
12   CONTROL SUB FUNCTIONS 
 
[4]   Setting the M code output function 
The following shows the settings to use the "M code output function".  
(1)  Set the M code No. in the positioning data "
Da.10
 M code".  
 
(2)  Set the timing to output the M code ON signal (X4, X5, X6, X7). 
 
Set the required value in the following parameter, and write it to the QD75MH. 
The set details are validated at the rising edge (OFF   ON) of the PLC READY 
signal (Y0). 
 
Buffer memory address 
Setting item 
Setting 
value 
Setting details 
Axis 
Axis 
Axis 
Axis 
 Pr.18  
M code ON signal 
output timing 
 
Set the timing to output the M code ON signal. 
    0: WITH mode 
    1: AFTER mode 
27  177 327 477 
 
                  Refer to Section 5.2 "List of parameters" for setting details. 
 
[5]   Reading M codes 
"M codes" are stored in the following buffer memory when the M code ON signal 
turns ON.  
 
Buffer memory address 
Monitor item 
Monitor 
value 
Storage details 
Axis 
Axis 
Axis 
Axis 
Md.25   Valid M code 
 
The M code No. (
Da.10
M code) set in the 
positioning data is stored. 
808 908 1008 1108 
 
                   Refer to Section 5.6 "List of monitor data" for information on the storage details. 
 
The following shows a PLC program example for reading the "
Md.25
 Valid M 
code" to the PLC CPU data register (D110). (The read value is used to command 
the sub work.) 
Read M codes not as "rising edge commands", but as "ON execution 
commands".  
 
M code ON signal
K1
D110
K808
H0
FROM
ON execution command
D110: valid M codes
Example