Appendix - 55 
MELSEC-Q
 
APPENDICES 
 
Trouble type 
Questions/Trouble 
Remedy 
No. 
When a JOG operation is 
attempted, an error results and the 
machine does not move. 
The "
Pr.31
JOG speed limit value" may be larger than 
the "
Pr.8
Speed limit value". 
Review the parameters and carry out the JOG operation 
again. 
34 
JOG operation 
Why does the positioning complete 
signal turns ON during the JOG 
operation? 
If a value other than "0" is set for "
Cd.16
Inching 
movement amount", the inching operation is carried out 
and the positioning complete signal turns ON. 
Confirm that the "
Cd.16
Inching movement amount" is 
set to "0". 
35 
Is it possible to count the pulses 
when the B phase is set to "1", and 
only A phase pulses are input? 
Possible. 
Set the "
Pr.24
Manual pulse generator input selection" 
to "3: PLS/ SIGN mode". It is possible to count the pulses 
when only A phase pulses are input. 
36 
Can a manual pulse generator 
other than the Mitsubishi MR-
HDP01 be used? 
Other manual pulse generators can be used if they 
conform to Section 3.4 "Specifications for input/output 
interfaces with external devices." 
The product warranty by the combination of QD75MH and  
manual pulse generator other than the MR-HDP01 is not 
possible. 
37 
Manual pulse 
generator operation 
Can one manual pulse generator 
be operated connected to several 
QD75MH modules? 
This is possible if the system conforms to the electrical 
specifications. 
The product warranty by the combination of several 
QD75MH and one manual pulse generator is not possible. 
38 
Current value 
changing 
The BUSY signal is not canceled 
by the current value changing.  
How can it be canceled? 
The BUSY signal may remain if the scan time is long.  
Use a complete signal to check whether the current value 
changing has been executed. 
39 
QD75 READY signal 
The QD75MH READY signal does 
not turn ON even when the PLC 
READY signal [Y0] is turned ON. 
"A parameter error" has occurred.  
Confirm the error No. in the error history, and correct the 
parameter. 
40 
M code ON signal 
Is there any problem with setting 
an M code ON signal OFF request 
in the next scan after the M code 
ON signal ON? 
The QD75MH checks the M code ON signal OFF request 
every "1.7ms", so there is a possibility that the M code ON 
signal OFF may be delayed by a maximum of "1.7ms" 
after the M code ON signal ON, even if an M code ON 
signal OFF request is set. 
41 
Module 
Error 537 (PLC READY signal 
OFF at positioning start) occurs 
after the QD75MH is replaced. 
(The PLC program is the same.) 
The internal parameters of the QD75MH may be different. 
Check if the QD75 READY signal [X0] turns ON when the 
PLC READY signal [Y0] turns ON. 
When the PLC READY signal is ON but the QD75MH 
READY signal is OFF, the parameter error has occurred. 
Check the error code and modify the parameter with the 
error. 
42 
The motor only rotates in one 
direction. 
The parameter settings on the QD75MH side may not 
match those on the servo side.  
Check the parameter settings. 
43 
Motor 
Can the current motor speed be 
monitored? 
The speed shown on the QD75MH monitor is calculated 
from the number of pulses output from the module. Thus, 
the actual motor speed cannot be monitored. 
( "
Md.22
Feedrate" monitors the commanded speed. It 
does not show the actual motor speed.) 
44