Page 8 - 3
Maintenance
Orbit™ 2000 Operation and Maintenance  Manual
 © GBC Films Group January 2001
MONTHLY
– Tighten and grease all roller chains
ANNUALLY
– Cleaning of the electrical assembly
E L E C T R IC A L
S H O C K
W A R N IN G :  Pow er  m u st  be  disconnected  to  m achine  at  fused  disconn ect!
– Dust can be removed by vacuuming the cabinet with a soft brush wand.
W A R N IN G
W A R N IN G :  N ever  use  com pressed  air  to  rem ove  dust  from   the
inside of the electrical cabinet.
– Inspection of the electrical assembly.
– Tightness of terminals
– Circuit breaker wires
– Loose wires
– Protective Circuit inspection
– Check whether protective connectors are tight. Tighten loose connections. The safety of
   protective circuits may be checked by feeding a current of at least 10 A (50 Hz) from the
   PELV source for at least 10 seconds. The test is done between the PE terminal and
   various points that are part of the protective circuit. See EN 60204-1, article 20.2.