4060
H
Online 
registration 
error
The online debug function is being executed 
by the other peripheral device.
• Execute the function again after the operation of the 
other peripheral device has ended.
• When the operation was suspended by the other 
peripheral device, execute the function again after 
executing it on the other peripheral device to normally 
complete the operation.
4061
H
Communication of the online debug function 
was unsuccessful.
• Execute communication after the registering the online 
debug function (e.g. online program change/trace/
conditional monitor).
• Execute again after checking the communication route 
such as the communication cable.
4063
H
The registered number of locked files 
exceeded the maximum value.
Execute again after file access by the other peripheral 
device has ended.
4068
H
Operation is disabled since the same 
operation is being executed from the other 
peripheral device.
Execute again after the operation from the other 
peripheral device is over.
406A
H
The drive (memory) number that cannot be 
handled (other than 0 to 4) was specified.
Check the specified drive and specify the correct drive.
4070
H
Circuit inquiry 
error
The program not yet corrected and the one 
corrected by online program change are 
different.
Execute read from PLC to make the program of the 
peripheral device the same as that of the CPU module, 
and then execute online program change again.
4080
H
Other errors
Request data error
Check the request data specified in the MC protocol, etc.
4081
H
The sort subject cannot be detected.
Check the data to be searched.
4082
H
The specified command is executing and 
therefore cannot be executed.
Execute the command again after the request from the 
other peripheral device is completed.
4083
H
An attempt was made to perform operation for 
the program not registered to the parameters.
Register the program to the parameters.
4089
H
An attempt was made to insert/delete the END 
instruction by online program change.
• Check the specified program file contents.
• Write the program after setting the CPU module to the 
STOP status.