Mitsubishi Electronics QSPCU ユーザーズマニュアル
12
TROUBLESHOOTING
12.5 Error codes returned to request source during communication with CPU module
12
- 70
9
EM
C AN
D
L
O
W
V
O
LT
AG
E
DI
RE
C
T
IV
E
S
10
LO
A
D
ING A
ND
INS
TA
LLA
T
ION
11
M
A
INT
E
NANCE
AND
IN
SP
ECT
IO
N
12
T
R
O
U
BL
ES
HO
O
T
IN
G
A
PPE
NDICES
INDEX
Table12.10 Error code (Continue)
Error code
(Hexadecimal)
Error item
Error details
Corrective action
4060
H
Online
registration
error
registration
error
The online debug function is being executed
by the other peripheral device.
by the other peripheral device.
• Execute the function again after the operation of the
other peripheral device has ended.
• When the operation was suspended by the other
peripheral device, execute the function again after
executing it on the other peripheral device to normally
complete the operation.
executing it on the other peripheral device to normally
complete the operation.
4061
H
Communication of the online debug function
was unsuccessful.
was unsuccessful.
• Execute communication after the registering the online
debug function (e.g. online program change/trace/
conditional monitor).
conditional monitor).
• Execute again after checking the communication route
such as the communication cable.
4063
H
The registered number of locked files
exceeded the maximum value.
exceeded the maximum value.
Execute again after file access by the other peripheral
device has ended.
device has ended.
4068
H
Operation is disabled since the same
operation is being executed from the other
peripheral device.
operation is being executed from the other
peripheral device.
Execute again after the operation from the other
peripheral device is over.
peripheral device is over.
406A
H
The drive (memory) number that cannot be
handled (other than 0 to 4) was specified.
handled (other than 0 to 4) was specified.
Check the specified drive and specify the correct drive.
4070
H
Circuit inquiry
error
error
The program not yet corrected and the one
corrected by online program change are
different.
corrected by online program change are
different.
Execute read from PLC to make the program of the
peripheral device the same as that of the CPU module,
and then execute online program change again.
peripheral device the same as that of the CPU module,
and then execute online program change again.
4080
H
Other errors
Request data error
Check the request data specified in the MC protocol, etc.
4081
H
The sort subject cannot be detected.
Check the data to be searched.
4082
H
The specified command is executing and
therefore cannot be executed.
therefore cannot be executed.
Execute the command again after the request from the
other peripheral device is completed.
other peripheral device is completed.
4083
H
An attempt was made to perform operation for
the program not registered to the parameters.
the program not registered to the parameters.
Register the program to the parameters.
4089
H
An attempt was made to insert/delete the END
instruction by online program change.
instruction by online program change.
• Check the specified program file contents.
• Write the program after setting the CPU module to the
• Write the program after setting the CPU module to the
STOP status.