Mitsubishi Electronics CR751-D ユーザーズマニュアル

ページ / 190
3-97 
  Magnet contactor control connector output (AXMC) for addition axes   
3 Controller
3.9 Magnet contactor control connector output (AXMC) for addition axes
When an additional axis is used, the servo ON/OFF status of the additional axis can be synchronized with the 
servo ON/OFF status of the robot itself by using the output contact (AXMC) provided on the rear or inside of the 
controller and configuring a circuit so that the power to the servo amplifier for the additional axis can be turned 
off when this output is open. 
An example circuit and an image of how to connect the controller connector are shown below. When you are using 
an additional axis, please perform appropriate circuit connections by referring to these drawings.
Refer to the separate "Additional axis interface Instruction Manual" for details on the additional axis function.
Note1)  you use the addition axis function as a user mechanism who became independent of the robot arm, please
do not connect this output signal. Servo-on of the user mechanism may be unable.
Fig.3-26 : Example of circuit for addition axes of Magnet contactor control output
MC2
NV
MC
MC1
内部回路へ
<コントローラ>
内部サーボ電源用
コンタクタ接点より
AXMC出力
<走行軸(付加軸)アンプボックス>
NV
2)コントローラ内蔵漏電遮断器(NV)の2次側より、
MC同期用電源を取り出す。
AXMC21
注2)
1)付加軸アンプボックス内蔵漏電遮断器(NV)の2次側より、コントローラ電源を取り出す。
AXMC11
注1)
88
CNUSRコネクタ
アンプ
DC24V
AXMC12
AXMC22
注2)
注1)コネクタとピン番号を以下に示します。
AXMC11
AXMC12
AXMC21
AXMC22
注2)ロボットがアラームの発生などでサーボOFFしたとき、本出力(接点)が開放します。
<接点容量>
DC24V/10mA~100mA
信号名
ピン番号
コネクタ
CNUSR2
45
19
44
20
CNUSR2
1) Get the power supply for the controller from the secondary terminal 
of short circuit breaker (NV) built in the addition axis amplifier box.
2) Get the power supply for the MC synchronization from the sec
-
ondary terminal of short circuit breaker (NV) built in the control
-
ler.
To the 
internal 
circuit
AXMC is output 
from the contact 
for internal servo 
power supplies.
<Controller>
CNUSR connector
Note1)
Note2)
Note2)
Amplifier
<Addition axis amplifier box>
<Addition axis amplifier box>
Signal
Connector
Pin number
Note1) Connector and Pin number
Note2) This output is opened, if the robot turns off the servo by occurrence of alarm etc.
<Electric specification>
DC24V/10mA to 100mA
[Note] In the customer's system, do not ground the + side of 24V power supply prepared by customer for connect to the con
-
troller. (related with emergency stop and parallel input/output) If it connects with the controller under the condition that 
the + side is grounded, it will lead to failure of controller.