IBM 42E ユーザーズマニュアル

ページ / 208
 
 NetBAY Power Distribution Units
 165
Line cords
The 2.5 m (8.2 ft) fixed line cord on the Rack PDU determines the connectivity of the 
Rack PDU.  The following table contains a list of the line cords that you can use with 
the Rack PDU:
Power cables
The Rack PDU comes with three power cables, that you use to connect to other 
M/PDU family devices, as listed in the following table:
Height
43 mm (1.7 in.)
Width
192 mm (7.5 in.)
Depth
221 mm (8.7 in.)
Weight
1.6 kg (3.5 lbs)
Operating temperatures
10
°
C–35
°
C (50
°
F–95
°
F) at 0–914 m (0–3000 ft)
10
°
C–32 
°
C (50
°
F–90
°
F
°
)
 
at 914–2133 m (3000–7000 ft)
Operating humidity
8–80% (non-condensing)
Rated voltage
100–120 V ac, 30 A, single-phase
200–240 V ac, 30 A, single-phase
200–240 V ac, 32 A, single-phase
200–240 V ac, 30 A, single-phase
380–415 V ac, 32 A, single-phase
Rated frequency
50–60 Hz
Maximum power rating
4800-6000 VA
Power inlet
One fixed line cord
Power outlets
Three IEC 320-C19 outlets rated at 16 A (VDE) / 20 A 
(UL/CSA)
Power Source
Line cord rating
Plug type
Line cord 
part #
100-127 V ac, 30 A, single-phase
127 V, 30 A
NEMA L5-30P
24P6846
200-240 V ac, 30 A, single-phase
250 V, 30 A
NEMA L6-30P
24P6847
200-240 V ac, 32 A, single-phase
250 V, 32 A
IEC 309-2P + Gnd
24P6848
200-240 V ac, 30 A, three-phase
250 V, 30 A
NEMA L21-30P
24P6844
380-415 V ac, 32 A, three-phase
415 V, 32 A
IEC 309-3P + N + Gnd
24P6845