Emerson MODBUS IP ユーザーズマニュアル
Modbus 485 and Modbus IP Protocols - Thermal Management Products
49
Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Table 14
Liebert HPC
™
(Chiller) - Status and Coil
Controller
Liebert iCOM
®
v4
Data Label
Status
Coil
Number
of Bits
Notes
Extra
Notes
Compressors
Compressor Not Stopping
Compressor Not Stopping
10001
—
1
Active on Alarm
1, 2
Compressor Superheat Over Threshold
10002
—
1
Active on Alarm
2
Compressor 1
Compressor Hours Exceeded
Compressor Hours Exceeded
10012
—
1
Active on Alarm
1, 2
Compressor High Head Pressure
10013
—
1
Active on Alarm
1, 2
Compressor Low Suction Pressure
10014
—
1
Active on Alarm
1, 2
Compressor Thermal Overload
10015
—
1
Active on Alarm
1, 2
Compressor Low Oil Pressure
10016
—
1
Active on Alarm
1, 2
Compressor Loss of Differential Pressure
10018
—
1
Active on Alarm
1, 2
Compressor Capacity Reduced
10019
—
1
Active on Alarm
1, 2
Compressor Capacity Normal
10020
—
1
Active on Alarm
2
Compressor Contactor Issue
10021
—
1
Active on Alarm
2
Compressor 2
Compressor Hours Exceeded
Compressor Hours Exceeded
10029
—
1
Active on Alarm
1, 2
Compressor High Head Pressure
10030
—
1
Active on Alarm
1, 2
Compressor Low Suction Pressure
10031
—
1
Active on Alarm
1, 2
Compressor Thermal Overload
10032
—
1
Active on Alarm
1, 2
Compressor Low Suction Pressure
10033
—
1
Active on Alarm
1, 2
Compressor Loss of Differential Pressure
10035
—
1
Active on Alarm
1, 2
Compressor Capacity Reduced
10036
—
1
Active on Alarm
1, 2
Compressor Capacity Normal
10037
—
1
Active on Alarm
2
Compressor Contactor Issue
10038
—
1
Active on Alarm
2
Compressor 4
Compressor Hours Exceeded
Compressor Hours Exceeded
10230
—
1
Active on Alarm
1, 2
Compressor High Head Pressure
10231
—
1
Active on Alarm
1, 2
Compressor Low Suction Pressure
10232
—
1
Active on Alarm
1, 2
Compressor Thermal Overload
10233
—
1
Active on Alarm
1, 2
Compressor Low Suction Pressure
10234
—
1
Active on Alarm
1, 2
Compressor Loss of Differential Pressure
10236
—
1
Active on Alarm
1, 2
Compressor Capacity Reduced
10237
—
1
Active on Alarm
1, 2
Compressor Capacity Normal
10238
—
1
Active on Alarm
2
Compressor Contactor Issue
10239
—
1
Active on Alarm
2
Condensers 1
Condenser Fan Issue
Condenser Fan Issue
10046
—
1
Active on Alarm
1, 2
Low Condenser Refrigerant Pressure
10047
—
1
Active on Alarm
1, 2
Condenser Max Fan Speed Override
10048
—
1
Active on Alarm
1, 2
Condensers 2
Condenser Fan Issue
Condenser Fan Issue
10058
—
1
Active on Alarm
1, 2
Low Condenser Refrigerant Pressure
10059
—
1
Active on Alarm
1, 2
Condenser Max Fan Speed Override
10060
—
1
Active on Alarm
1, 2
Condensers 4
Condenser Fan Issue
Condenser Fan Issue
10066
—
1
Active on Alarm
1, 2
Low Condenser Refrigerant Pressure
10067
—
1
Active on Alarm
1, 2
Condenser Max Fan Speed Override
10068
—
1
Active on Alarm
1, 2