28   Installation and start-up 
UM5C06D   ( 169-2071-504 )   P0831010   Standard 7.00   May 2001 
Verification 
After completing the wiring of the power shelf perform the following: 
Procedure 2 - Verification 
Step Action 
Verify that the power shelf has been mechanically secured. 
Verify that all the wiring performed is correct by using a voltmeter. 
Verify that all connections are mechanically correct (that is, tight, correct 
connector, correct marking etc.) 
Reinstall the AC and DC junction box cover on the left and right sides. 
end
 - 
Installing the rectifier 
The NT5C06D rectifier is a plug-in unit intended for use in the MPS75 
power shelf. 
Procedure 3 - Rectifier installation procedure 
Step Action 
Release the clamping bar by loosening the two captive screws 
Remove the blank panel for the rectifier to be installed (place a finger in the 
hole, lift up, pull forward, then lower to disengage upper tabs from the shelf 
top). Store the panel at the bottom of the shelf, under the rectifier. 
Ensure that both AC and DC circuit breakers are in the OFF position. 
Use a voltmeter to verify that the AC supply at the input of the shelf is 208 
/ 240 V AC nominal. 
Carefully slide the rectifier in position on top of the stored blank panel. 
Insure that the rectifier is firmly slid and seated into position. 
Reinstall the clamping bar by securing the two captive screws. 
end
 
Factory setting 
The rectifier is factory set as indicated in Table 7. 
Table 7 - Rectifier settings 
 
Load 
Sharing 
Slope load sharing method 
Rectifier Output Voltage (FLOAT) 
54.5 V DC  ± 0.1 V 
Rectifier Output Voltage (EQUALIZE) 
55.2 V DC  ± 0.1 V 
Rectifier High Voltage Shutdown (HVSD)  59.0 V DC  ± 0.1 V 
Rectifier Output Current Limit 
30 A 
± 0.5 A