Installation Drawings
38
6.0
I
NSTALLATION
 D
RAWINGS
The diagrams in this section illustrate the key mechanical and electrical characteristics of the Liebert 
NX UPS System cabinets.
Figure 21 Liebert NX 40-120kVA dimensional view—front and left side
39.6mm
(1.6")
997mm
(39.3")
360mm
(14.2")
Center of Gravity 
Without Internal Battery
Left Side
2000 mm
(78.7")
Front
600 mm
(23.6")
301mm 
(11.9")
Liquid 
Crystal 
Display
1. All dimensions are in millimeters (in.).
2. Eight-inch minimum clearance above unit 
required for air exhaust.
3. Keep cabinet within 15 degrees of vertical 
while handling.
4. Top and bottom cable entry available through 
removable access plates. Remove access plate, 
punch to suit conduit size and replace.
5. Color - black.
6. Unit bottom is structurally adequate for 
forklift handling.
7. Open door to replace air filter, washable type.
8. M10 threaded mounting holes used for 
seismic anchoring or floor stand.
NOTE: If floor stand is used, the weight of the 
unit must be supported under all casters.
9. Each mounting location is supported by (2) 
10ga. (.135") galvanized steel. The threaded 
insert is approximately 3/4" deep. Mounting 
holes are underneath unit base; mounting 
bolts must be threaded into unit.
10. Includes side panel. Side panels must be 
removed from adjacent units that are bolted 
together.
11. Leveling feet are not designed to carry the full 
weight of the cabinet.
12. Finger-tighten leveler against the floor, then 
tighten with a wrench less than 2 turns for 
friction fit against floor.