Emerson 480V ユーザーズマニュアル

ページ / 112
Operating Instructions
78
9.1.1 Circuit Breakers
The UPS can be isolated by means of circuit breakers, mounted inside the cabinet and accessible after 
opening the front door.
The location of the UPS power switches is shown in Figure 59.
Figure 59 Circuit breakers
The UPS unit circuit breakers are CB1, CB2, CB3 and CB5.
• CB1—Main Input circuit breaker; connects the utility supply to the UPS main input.
• CB2—Bypass circuit breaker; connects the utility supply to the UPS bypass.
• CB3—Maintenance Bypass breaker; connects the utility supply to the UPS maintenance bypass.
• CB5—Output breaker; connects inverter or bypass to the external output transformer or power 
distribution panel.
9.2
UPS Startup
The Liebert NX must be fully installed and commissioned before startup, and external power isolators 
must be closed. Once those general conditions are met, the UPS may be started.
9.2.1 Startup Procedure
To start the UPS from a fully powered-down condition:
1. Open the UPS door to gain access to the main input circuit breakers.
2. Close CB1, CB2 and CB3 (CB5 is open).
The main input contactor closes automatically and the LCD begins to show start-up
screens. The Rectifier indicator flashes green while the rectifier is starting up. It stops flashing 
and becomes solid green about 30 seconds after the rectifier enters the normal operation state.
!
WARNING
During this procedure the output terminals will become live.
If any load equipment is connected to the UPS output terminals, please check with the load 
user and ascertain whether it is safe to apply power to the load. If the load is not ready to 
receive power, then ensure that it is safely isolated from the UPS output terminals.