HP (Hewlett-Packard) A6585A ユーザーズマニュアル

ページ / 120
 
Alert messages  104 
Alert messages 
UPS alarms 
This management module enables you to send an email notification or SNMP trap to specified recipients 
if a certain alert situation prevails. 
The following table lists all message texts and a description of each alarm. 
          
Alarm text 
Description 
Battery Discharged 
 
The battery is not fully charged. 
 
The battery has been discharged to its maximum discharged state. 
 
The UPS was on battery for long enough to exhaust the battery capacity 
and has shut down. 
Batteries Disconnected 
The UPS detects that at least one of the batteries is not connected. Backup 
power is either gone or considerably reduced. 
Battery Failure 
 
The battery contactor/breaker is open. 
 
The battery voltage has exceeded a predetermined limit. Operating with 
this alarm set can cause permanent battery or system damage. 
 
A battery problem has been detected. 
 
A battery test has been executed, and the battery failed the test. 
 
The charger circuit has detected possible bad batteries or an open 
circuit in connections to the batteries. 
Battery Low 
The battery voltage level has dropped below the predetermined "low battery 
warning" level. 
Bypass Failure 
The bypass input voltage is not available for transfer. This condition might 
be caused by over or under voltage, over or under frequency, out of phase 
lock, or other reasons. 
Bypass ON Auto 
The UPS is on bypass, and the critical load does not have power protection. 
Bypass ON Manual 
A user has flipped a switch (for example, Maintenance Bypass) that 
bypasses the UPS.  
Check Breaker 
 
The inverter output contactor/breaker is open. 
 
The rectifier/charger input breaker is open. 
Electronics Module 
Failure 
For an "n+1" parallel system, one of the power modules has failed. 
EPO Initiated 
The UPS has shut down because of the activation of the remote EPO signal.